| SG SeriesTM UPS PLUS® |
|
|
| 1kVA to 3kVA | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Model Number |
|
|
|
|
|
|
|
| ||||||||||
|
| Nominal VA |
|
|
| 1000 |
| 2000 |
|
| 3000 |
|
| |||||||
|
| Electrical Input |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Nominal AC Voltage |
|
| 120V |
| 230V |
| 120V |
|
| 230V |
| 120V |
|
| 230V |
| ||
|
| AC Voltage Range |
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
| 6.9 | 3.6 |
| 14.2 |
|
| 7.5 | 21.4 |
|
| 11.2 |
|
| |||
|
| Frequency |
|
|
|
|
| 50/60 Hz ± 5% |
|
|
|
|
|
|
| |||||
|
| Power Factor Correction |
|
|
|
|
|
| > 0.95 |
|
|
|
|
|
|
|
|
| ||
|
| Efficiency (Typical) |
|
| > 89% |
|
|
|
| > 86% |
|
|
|
|
| |||||
|
| Electrical Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Watts |
|
|
| 700 | 700 |
| 1400 |
|
| 1400 | 2100 |
|
| 2100 |
|
| ||
|
| AC Voltage |
|
|
| 100V |
| 200V |
| 100V |
|
| 200V |
| 100V |
|
| 200V |
| |
|
| (Switchable) |
|
|
| 110V |
| 220V |
| 110V |
|
| 220V |
| 110V |
|
| 220V |
| |
|
|
|
|
|
| 115V |
| 230V |
| 115V |
|
| 230V |
| 115V |
|
| 230V |
| |
|
|
|
|
|
| 120V |
| 240V |
| 120V |
|
| 240V |
| 120V |
|
| 240V |
| |
|
| Frequency |
|
|
|
|
|
|
| 50/60 Hz (Auto Tracking ) |
|
|
|
|
|
|
| |||
|
| Frequency Stability |
|
|
|
|
|
| ± 0.3% (Battery Mode) |
|
|
|
|
|
|
| ||||
|
| Voltage Regulation |
|
|
|
|
|
| ± 2% |
|
|
|
|
|
|
|
|
|
| |
|
| Step Load Change |
|
|
|
|
|
| ± 7% for 100% load variation |
|
|
|
|
|
|
| ||||
|
| Harmonic Dis tortion |
|
|
|
| < 3% Linear Load, < 5% Non |
|
|
|
|
|
|
| ||||||
|
| Overload |
|
|
|
|
|
|
| 105% load for 50 Seconds |
|
|
|
|
|
|
| |||
|
| Crest Ratio |
|
|
|
|
|
|
| 3:1 |
|
|
|
|
|
|
|
|
|
|
|
| Battery |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DC Voltage |
|
|
| 48V |
| 72V |
|
|
| 96V |
| |||||||
|
| Type |
|
|
|
|
| 12V, 7AH Sealed Lead Acid Maintenance |
|
|
|
|
| |||||||
|
| Back Up Time | @ Full Load | 6 Minutes |
| 7 Minutes |
|
| 5.5 Minutes |
| ||||||||||
|
|
| @ 1/2 Load | 19 Minutes |
| 20 Minutes |
| 15 Minutes |
| |||||||||||
|
| Recharge Time |
|
|
|
|
|
|
| 8 Hours to 90% |
|
|
|
|
|
|
|
| ||
|
| Battery times are approximate. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Transfer Time |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Line Fails/Recovers |
|
|
|
|
|
| Zero |
|
|
|
|
|
|
|
|
|
| |
|
| UPS to Bypass or Reverse |
|
|
|
| < 4ms |
|
|
|
|
|
|
|
| |||||
|
| After Overload |
|
|
|
|
|
|
| Auto Transfer to UPS |
|
|
|
|
|
|
| |||
|
| Electrical Connecti ons |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Input |
|
|
| 6’ Cord with |
| 6’ Cord with |
| 6’ Cord with |
| 6’ Cord with |
| 6’ Cord with |
|
| 6’ Cord with |
| ||
|
|
|
|
|
|
| Schuko or |
|
| Schuko or |
|
|
| Schuko or |
| |||||
|
|
|
|
|
|
|
|
|
| L5 |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| Output |
|
|
| (4) |
| (4) IEC320 |
| (4) |
| (4) IEC 320 |
| (4) |
|
| (4) IEC 320 |
| ||
|
| Contact the factory fo r other input/output options. . |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| Environmental |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Operating Temperature |
|
|
|
|
|
| 0º C - 40º C (32º F to 104º F) |
|
|
|
|
|
|
| ||||
|
| Humidity |
|
|
|
|
| 10% to 95% Non – Condensing |
|
|
|
|
|
|
| |||||
|
| Altitude |
|
|
|
|
|
|
| 7,000 Feet |
|
|
|
|
|
|
|
| ||
|
| Cooling |
|
|
|
|
|
|
| Low Velocity Forced Air Fans |
|
|
|
|
|
|
| |||
|
| Audible Noise @ 1 Meter |
|
|
|
| < 55dBA |
|
|
|
|
|
|
|
| |||||
|
| Controls and Indicators |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| LED |
|
|
| Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery | & Load Capacity Level |
| ||||||||||||
|
| Audible Alarms |
|
|
| DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp. , Over Load, Fault Alarm |
| |||||||||||||
|
| Communications |
|
|
|
|
|
|
|
|
|
| ||||||||
|
| Mechanical |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| UPS Module Dimensions | 3.51 x 16.8 x 17.7 (89 x 426.7 x 449.5) |
| 3.51 x 16.8 x 17.7 | (89 x 426.7 x 449.5) |
| |||||||||||||
|
| Battery Pack Dimensions | Internal to UPS Module |
| 3.51 x 16.8 x 17.7 | (89 x 4 26.7 x 449.5) External to UPS Module |
| |||||||||||||
|
| H x W x D | Inches (mm) |
|
|
|
| 2kVA & 3kVA are (2) cabinet configuration, Hot Swappable Batteries |
| |||||||||||
|
| UPS Module Weight | lb. (kg) | 39 | (18) |
| 29 | (13) |
| 29 | (13) |
|
| |||||||
|
| Battery Pack Weight | lb. (kg) | Internal |
| 53 | (24) |
| 64 | (29) |
|
| ||||||||
|
| Agency Listing |
|
|
| UL 1778, CUL, |
| CE available with |
| UL 1778, CUL, |
| CE available | UL 1778, CUL, |
|
| CE available |
| |||
|
|
|
|
|
|
|
|
|
| with Schuko |
|
| with Schuko |
|
| |||||
|
|
|
|
|
| FCC Class A |
| Schuko plug only |
| FCC Class A |
|
|
| FCC Class A |
|
|
| |||
|
|
|
|
|
|
|
|
|
| plug only |
|
|
| plug only |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Available Options |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Option A |
|
|
| 60 Hz to 50 Hz Frequency Conversion |
|
|
|
|
|
|
|
|
|
|
| |||
|
| Option B |
|
|
| 50 Hz to 60 Hz Frequency Conversion |
|
|
|
|
|
|
|
|
|
|
| |||
|
| Option C |
|
|
| SNMP/HTTP Network Card (Internal) |
|
|
|
|
|
|
|
|
|
|
| |||
|
| Option D |
|
|
| Standard Contact Closure Interface Card |
|
|
|
|
|
|
|
|
|
|
| |||
|
| External Battery Packs |
|
| Extended Run Time Battery Packs (minutes to hours) |
|
|
|
|
|
|
|
|
|
| |||||
|
| Slide Rails |
|
|
| Heavy Duty Roller Bearing Slide Rails for side mounting |
|
|
|
|
|
|
|
|
|
| ||||
©2003 Falcon® Electric, Inc. All rights reserved. Falcon® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc. |
|
|
|
|
|
|
| |||||||||||||
All other brand names and trademarks are the property of their respective owners. |
|
|
|
|
|
|
|
|
|
|
| |||||||||
The information and specifications stated in this document are subject to change without notice. |
|
|
|
|
|
|
|
Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720
www.falconups.com - email: sales@falconups.com
22