Falcon SG1KRM-1TU Communications Interfaces, Location, Supported Protocols, RS-232 Interface

Page 17

CHAPTER 5

COMMUNICATIONS INTERFACES

RS-232 INTERFACE

Location:

The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector.

Supported Protocols

UPSILON 2000 & SEC Smart Mon

BAUD RATE -------

2400bps

DATA LENGTH----

8 bits

STOP BIT-----------

1 bit

PARITY--------------

None

1

2

6

TX

GND

3

7

GEN

4

8

RX

 

 

59

DB-9 Connector Pin Assignment

Pin #

Function explanation

I/O

9

RS 232 Rx

INPUT

6

RS 232 Tx

OUTPUT

7

Ground

 

 

 

 

 

 

 

CAUTION

When making a connection between a computer and the UPS RS-232 port, always use the green cable supplied with the UPS due to the propriatary pin- out of the RS-232 port.

CAUTION

There are communications options that WILL DISABLE the RS-232 port and render it inoperable. The options are as follows:

a.Internal SNMP/HTTP agent option installed into the UPS communications option slot.

The following options WILL NOT affect the operation of the RS-232 port:

a.Falcon Opto Coupler based signal interface board installed in the communications option slot.

b.Any Falcon relay based, dry contact signal interface board installed in to the communications option slot.

CAUTION

DB-9 Signals are not isolated and intended for connection to like RS-232 interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!

15

Image 17
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Extended Battery Bank Option Input Power Factor CorrectionTrue Regenerative On-Line Design Microprocessor ControlRackmount UPS Mounting Instructions --- Important SG Rackmount Installation InstructionsGreen Mode Disabled Enabled No Battery Backup is Provided When in this Mode100-120V 200-240V Models OnlyUPS Battery Module Interconnect WiringPage Slide Mounting Details Optional Slide Mounting KIT SgrmkitFor 1KVA Models SG Rackmount Extended Battery Bank Selection GuideOperation UPS Front Panel Indicator and Function KeysInverter Indicator LED Category two alarms Audible Alarms Category one alarms All models Front & Rear Panel DetailsSG1KRM-1TU SG1KRM-2TUSG2KRM-2TU & SG3KRM-2TU Typical Rear Panel Overview SG2KRM-1TU & SG3KRM-1TUTypical Rear Panel Overview Location Communications InterfacesSupported Protocols RS-232 InterfacePIN & Jumper Assignment for the Falcon DRY Contact & Opto Coupler Interface Board OptionsUA88374 Relay Option Board UA88376 Relay Option BoardTypical Falcon Opto-coupler Interface Card No-bypass signalPIN Assignment for the Falcon UA88373 OPTO-COUPLER Option BoardBattery Replacement Care & MaintenanceBattery Life vs. Temperature FCC Considerations Storing the UPS and BatteriesRequesting Technical Information or Support Technical SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportGeneral Provisions Limited NEW Product Warranty AgreementSG SeriesTM UPS Plus