Eaton Electrical 34003991EN/EB user manual Display in the list of current alarms

Page 63

The low alarm disappears when the value returns above the Low threshold + Hysteresis value

Input #1 and Input #2: Enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning, generator unit, etc.). Max. length is 28 characters.

when closed and when open: are the names associated to the two contact positions. (e.g.: "open" and "closed" for a door, "On" and "Off" for a generator).

Each status change triggers a notification if enabled.

When the Notification box is enabled, the following functions are activated for each event selected:

display in the list of current alarms

Consideration in the UPS log

SNMP trap generation

notification by e-mail (if the Environment sensor notification option is enabled in the e-mail notification page)

The list of messages is given in the appendix

System shutdown can be triggered for each notification if this option is enabled. If notification is disabled, the Shutdown option cannot be used.

Export settings to file: Enables exportation ("Download" button) and saving of card configuration information.

Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button) of card configuration information.

Security: The user must be identified to access this page.

Network Management Card – User Manual

34003991EN/EB

Page 63/118

Image 63
Contents Network Management Card Contents Configuration VIA RS232 Server ProtectionIndustrial Network Management Card Inmc Option Glossary Jbus TableAppendices MGE MIBGeneral Presentation Eaton Network SolutionProtection of the computers/servers Connecting the UPS to the Ethernet networkConnection Supervision of the UPSs over the networkCompatibility with UPSs How to connect UPS / agent / networkSetting up the protection Presentation of the Network Management Card NMCDirect sending of E-mail Sending text messages SMSEnvironment Sensor option EMC Compatibility Technical dataHardware characteristics ConfigurationList of ports used AdministrationNetwork Environment sensorMIB Management Information Base BOOTP/DHCP Default parametersInstallation Unpacking and check on contentsIndications Installation in the UPS LEDACT Sensor installation option Configuration Configure IP parametersEaton Network Management Card Your network is equipped with a Dhcp server Your network is not equipped with a Dhcp server Test after configurationOptimising the performance of your browser Supervision and administration by browserUPS properties UPSUPS zone general information on the UPS 23/118 24/118 25/118 26/118 UPS status zone Essential information Viewing the modules 29/118 Viewing the alarms Alarm table for modular UPS Viewing the About your UPS window On-line help UPS control 35/118 36/118 UPS weekly schedule programming Shutdown parameters For the main outlet Master by default Measurements Event log System log Email Notification Notification44/118 Mail Message Settings 46/118 Configuration Network settings 49/118 System 51/118 Notified Applications 53/118 Central shutdown configuration 55/118 Access controlTLS Date and time 58/118 Firmware upload Environment Sensor option CharacteristicsEnvironment Status Environment Settings Display in the list of current alarms 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Utility failure Start of the shutdown sequence Shutdown duration Shutdown when backup time is less thanControlled outlets Protection of a server connected to a controlled outletLoad shedding or sequential shutdown Sequential startup Different server and UPS shutdown sequences70/118 Settings Shutdown management with 2 NMC boardsShutdown Duration Configuration via RS232 Choice 1 Restart / Reset Choice 2 Network ConfigurationChoice 1 Read Network settings Choice 3 Set Ethernet speed Choice 2 Modify Network settingsChoice 3 Lost password / Set Login Password to Default Choice 4 Return to Default Configuration Industrial Network Management Card Inmc option PresentationOverview Functions JBUS/MODBUS Technical characteristics1 RS232 link configuration and connection Installation2.1 RS485 connection 2 RS485 link configuration and connection81/118 2.2 RS485 link configuration for 2 wires connexion 83/118 2.3 RS485 link configuration for 4 wires connexion 85/118 Configuration of the JBUS/MODBUS communication parameters Choice 2 Modify Jbus settings Choice 1 Display Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus frames Additional Web pages Jbus table Data for Pulsar 700 / 1000Status table Measurements table Data for Pulsar M 2200 94/118 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT 96/118 Data for Pulsar MX frame 15 Modular fault table 99/118 100/118 101/118 5.1 Status table Sensor data103/118 Read of the personalization table Other data Tables of alarms and events Table of alarmsAppendices UPS OK If the UPS is modular UPS, for each module Table of UPS events 110/118 Table of system alarms MGE MIB Snmp objects113/118 1yes 2no 1,4,1 MIB Trap Table des Traps116/118 Glossary MIB Management Information BaseNetwork Management Proxy Smtp Simple Mail Transfer Protocol NMS Network Management Station SnmpNSM Network Shutdown Module Snmp Simple Network Management Protocol