7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT
7.4.3.1 Status table
Status description | Status to 0 | Status to 1 | Word (hex) | Bit |
|
|
|
|
|
Load protected | no | yes | 40 | 0 |
UPS coupled | no | yes | 40 | 1 |
Unit general alarm | no | yes | 40 | 2 |
UPS in backup | no | yes | 40 | 4 |
Battery low warning | no | yes | 40 | 5 |
Low battery | no | yes | 40 | 6 |
Operation on static switch | no | yes | 40 | 7 |
Communication fault | absent | present | 40 | 9 |
UPS overload | no | yes | 40 | A |
Emergency stop | absent | present | 40 | B |
Battery to be checked | no | yes | 40 | D |
Device ventilation fault | no | yes | 40 | E |
Manual bypass switch (Q3BP) | open | closed | 41 | 6 |
UPS in “eco” mode | no | yes | 41 | 7 |
Battery present | absent | present | 42 | 0 |
Mains 1 voltage out of tolerance | no | yes | 44 | 8 |
Mains 1 fuse fault | no | yes | 44 | 9 |
Mains 1 frequency out of tolerance | no | yes | 44 | B |
Redundancy lost | no | yes | 45 | 7 |
Maintenance position | no | yes | 46 | 1 |
Mains 2 overload | no | yes | 46 | 5 |
Mains 2 thermal overload | no | yes | 46 | 6 |
Output on bypass | no | yes | 46 | 7 |
Mains 2 frequency out of tolerance | no | yes | 46 | 9 |
Mains 2 voltage out of tolerance | no | yes | 46 | A |
Phase M2 out of tolerance | no | yes | 46 | B |
Mains 2 internal fault | absent | present | 47 | 2 |
Charger general fault | no | yes | 49 | 0 |
Battery charge | no | yes | 49 | 1 & 3 |
Converter fault | no | yes | 4A | 1 |
Inverter major fault | no | yes | 4C | 1 |
Inverter overload | no | yes | 4C | 2 |
Inverter thermal overload | no | yes | 4C | 3 |
Inverter limitation | no | yes | 4C | 4 |
UPS fuse fault | absent | present | 4C | 5 |
|
|
|
|
|