Eaton Electrical 34003991EN/EB user manual Utility failure Start of the shutdown sequence

Page 66

Utility failure

Start of the shutdown sequence

UPS Shut off

Battery

Shutdown after :

 

 

 

 

 

capacity

 

 

 

 

Delay before

 

 

 

shutdown

 

 

100%

 

 

 

 

Remaining autonomy

 

 

 

If remaining time under

Shutdown if

Shutdown duration

 

remainig

 

 

 

capacity under

 

 

 

0%

 

 

t

 

 

 

 

Card parameters

UPS parameters

5.1.1.1Backup time before initiating the shutdown procedure (Shutdown After – Shutdown Timer)

When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown.

This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time.

Note 1:

The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown Module"set- up" menu of each Network Shutdown Module) launched when the UPS switches to battery.

Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power restoration if only this system was shut down).

5.1.1.2Initiating the shutdown procedure when the battery level is lower than: (If Capacity under)

When the card detects that the remaining backup time percentage is less than the configured level, the shutdown sequence is started.

By default, this value is set at 20%.

Note:

The UPS already manages an equivalent parameter for the end of backup pre-alarm.

The card does not accept values less than that programmed in the UPS.

Check the UPS documentation.

Network Management Card – User Manual

34003991EN/EB

Page 66/118

Image 66
Contents Network Management Card Contents Configuration VIA RS232 Server ProtectionIndustrial Network Management Card Inmc Option MGE MIB Jbus TableAppendices GlossaryEaton Network Solution General PresentationConnecting the UPS to the Ethernet network Protection of the computers/serversSupervision of the UPSs over the network ConnectionPresentation of the Network Management Card NMC How to connect UPS / agent / networkSetting up the protection Compatibility with UPSsDirect sending of E-mail Sending text messages SMSEnvironment Sensor option Configuration Technical dataHardware characteristics EMC CompatibilityEnvironment sensor AdministrationNetwork List of ports usedMIB Management Information Base Default parameters BOOTP/DHCPInstallation Unpacking and check on contentsIndications Installation in the UPS LEDACT Sensor installation option Configuration Configure IP parametersEaton Network Management Card Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverSupervision and administration by browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS 23/118 24/118 25/118 26/118 UPS status zone Essential information Viewing the modules 29/118 Viewing the alarms Alarm table for modular UPS Viewing the About your UPS window On-line help UPS control 35/118 36/118 UPS weekly schedule programming Shutdown parameters For the main outlet Master by default Measurements Event log System log Notification Email Notification44/118 Mail Message Settings 46/118 Configuration Network settings 49/118 System 51/118 Notified Applications 53/118 Central shutdown configuration Access control 55/118TLS Date and time 58/118 Firmware upload Characteristics Environment Sensor optionEnvironment Status Environment Settings Display in the list of current alarms 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Utility failure Start of the shutdown sequence Shutdown when backup time is less than Shutdown durationControlled outlets Protection of a server connected to a controlled outletLoad shedding or sequential shutdown Different server and UPS shutdown sequences Sequential startup70/118 Settings Shutdown management with 2 NMC boardsShutdown Duration Configuration via RS232 Choice 1 Restart / Reset Choice 2 Network ConfigurationChoice 1 Read Network settings Choice 2 Modify Network settings Choice 3 Set Ethernet speedChoice 3 Lost password / Set Login Password to Default Choice 4 Return to Default Configuration Industrial Network Management Card Inmc option PresentationOverview Functions Technical characteristics JBUS/MODBUSInstallation 1 RS232 link configuration and connection2 RS485 link configuration and connection 2.1 RS485 connection81/118 2.2 RS485 link configuration for 2 wires connexion 83/118 2.3 RS485 link configuration for 4 wires connexion 85/118 Configuration of the JBUS/MODBUS communication parameters Choice 1 Display Jbus settings Choice 2 Modify Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus frames Additional Web pages Jbus table Data for Pulsar 700 / 1000Status table Measurements table Data for Pulsar M 2200 94/118 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT 96/118 Data for Pulsar MX frame 15 Modular fault table 99/118 100/118 101/118 Sensor data 5.1 Status table103/118 Read of the personalization table Other data Tables of alarms and events Table of alarmsAppendices UPS OK If the UPS is modular UPS, for each module Table of UPS events 110/118 Table of system alarms Snmp objects MGE MIB113/118 1yes 2no 1,4,1 Table des Traps MIB Trap116/118 Glossary MIB Management Information BaseNetwork Management Proxy Snmp Simple Network Management Protocol NMS Network Management Station SnmpNSM Network Shutdown Module Smtp Simple Mail Transfer Protocol