Utility failure | Start of the shutdown sequence | UPS Shut off | |
Battery | Shutdown after : |
|
|
|
|
| |
capacity |
|
|
|
| Delay before |
|
|
| shutdown |
|
|
100% |
|
|
|
| Remaining autonomy |
|
|
| If remaining time under | ||
Shutdown if | Shutdown duration |
| |
remainig |
|
|
|
capacity under |
|
|
|
0% |
|
| t |
|
|
| |
| Card parameters | UPS parameters |
5.1.1.1Backup time before initiating the shutdown procedure (Shutdown After – Shutdown Timer)
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown.
This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time.
Note 1:
The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown Module"set- up" menu of each Network Shutdown Module) launched when the UPS switches to battery.
Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power restoration if only this system was shut down).
5.1.1.2Initiating the shutdown procedure when the battery level is lower than: (If Capacity under)
When the card detects that the remaining backup time percentage is less than the configured level, the shutdown sequence is started.
By default, this value is set at 20%.
Note:
The UPS already manages an equivalent parameter for the end of backup
The card does not accept values less than that programmed in the UPS.
Check the UPS documentation.
Network Management Card – User Manual | 34003991EN/EB | Page 66/118 |