Eaton Electrical 10000L(XL), 6000L(XL) user manual Option

Page 11

Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper between JP1 and JP2 must be removed.

Option: 2

Connection Details of Output Terminals.

Connect Output Line 1 and Neutral2 by 10AWG (6mm2) for 240V / 6KVA Load. Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper between JP1 and JP2 must be removed.

2.3Operating procedure for connecting the long backup time model UPS with the external battery

1.The nominal DC voltage of external battery pack is 240VDC. Each battery pack consists of 20 pieces of 12V maintenance free batteries in series. To achieve longer back time, it is possible to connect multi-battery packs, but the principle of same voltage, same typeshould be strictly followed.

2.The connector of the external battery cable is used to plug into the external battery socket of the UPS, the other end of the external battery cable is made of three open wires with ring terminals to connect with the external battery pack(s). The procedure of installing battery bank should be complied with strictly. Otherwise you may encounter the hazardous of electric shock.

9

Image 11
Contents Uninterruptible Power Supply Contents System and model description Description of commonly used symbolsBrief introduction Nation and Explanation AppearancePage Electrical performance Unpacking and inspection InstallationPage Page Option Option Page Parallel operation Operation Operation and Operating modePage Operating mode Function Page RS232 interface GND Battery maintenance Replacement Problem Possible cause Solution TroubleshootingUPS Set the bypass breaker in on position Appendix 1: display panel Appendix 2: The corresponding form of the LED Display Page 614-03753-01