Eaton Electrical 6000L(XL), 10000L(XL) user manual Electrical performance

Page 6

Electrical performance

Input

Model

 

Voltage

Frequency

 

Power Factor

 

 

 

 

 

 

 

 

 

6000L(XL)/

 

Single-phase

(46~54)/(56~64)Hz

 

>0.98 (Full load)

10000L(XL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

Power

 

Frequency

Distortion

Overload capacity

Current

regulation

factor

 

tolerance

crest ratio

 

 

Synchronized

 

105%130% load

 

 

 

 

transfers to bypass

 

 

 

(46~54)/(56~64)Hz

 

mode after 10

 

 

 

 

in Line mode(AC

THD<3%

minutes.

 

 

±4%

0.7lag

mode)

Full load

>130% load transfers

3:1

 

 

 

 

(linear

maximum

 

 

±0.1% of normal

load)

to bypass mode after

 

 

 

frequency in

 

1 second and

 

 

 

 

Battery mode.

 

shutdown the output

 

 

 

 

 

 

after 1 minutes

 

 

 

 

 

 

 

 

 

 

Operating environment

Temperature

Humidity

Altitude

Storage temperature

 

 

 

 

0~40

<95%

<1000m

-15~40

 

 

 

 

Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following :

Altitude (M)

1000

1500

2000

2500

3000

3500

4000

4500

5000

Deratingpower

100%

95%

91%

86%

82%

78%

74%

70%

67%

4

Image 6
Contents Uninterruptible Power Supply Contents Description of commonly used symbols Brief introductionSystem and model description Appearance Nation and ExplanationPage Electrical performance Installation Unpacking and inspectionPage Page Option Option Page Parallel operation Operation and Operating mode OperationPage Operating mode Function Page RS232 interface GND Battery maintenance Replacement Troubleshooting Problem Possible cause SolutionUPS Set the bypass breaker in on position Appendix 1: display panel Appendix 2: The corresponding form of the LED Display Page 614-03753-01