2)To power on the UPS by simply pressing the ONbutton continuously for more than 1 second.

3)When being powered on, the UPS will perform self-diagnosis, with the load/battery level LEDs turned on and then off one after another in ascending order. A few seconds later, the INV LED is turned on, the UPS is already running in Utility Power mode. If the utility power is abnormal, the UPS will operate in battery mode without output interruption of the UPS.

2.Turn on the UPS with no utility power supplied (in Battery mode)

1)Press the ONbutton continuously for more than 1 second to power on the UPS. For long back up time model (XLmodel), please make sure that the battery breaker is in ONposition.

2)During the course of starting up, the UPS has the same action as if it is connected to utility power except that the utility power LED is not turned on and the battery LED is turned on instead.

3.Turn off the UPS with utility power supplied (in Line mode/AC mode)

1)Press the OFFbutton continuously for more than 1 second to turn off the inverter of the UPS immediately.

2)When being powered off, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off one after another in ascending order, then the INV LED will be turned off and Bypass LED will be turned on. The UPS is working in Bypass mode.

3)Upon completion of the above to turn it off, output of electric current of the UPS is still present. In order to cut off the output from the UPS, simply cut off the utility power supply and the UPS will perform self-diagnosis, finally not any display is shown on the display panel and no voltage output is available from the UPS output.

4.Turn off the UPS with no utility power supplied (in Battery mode)

1)Press the OFFbutton continuously for more than 1 second

13

Image 15
Contents Uninterruptible Power Supply Contents Description of commonly used symbols Brief introductionSystem and model description Nation and Explanation AppearancePage Electrical performance Unpacking and inspection InstallationPage Page Option Option Page Parallel operation Operation Operation and Operating modePage Operating mode Function Page RS232 interface GND Battery maintenance Replacement Problem Possible cause Solution TroubleshootingUPS Set the bypass breaker in on position Appendix 1: display panel Appendix 2: The corresponding form of the LED Display Page 614-03753-01