To connect the load with the UPS, please turn off all the loads first, then perform the connection and finally turn on the loads one by one.

No matter the UPS is connected to the utility power or not, the output of the UPS may have electricity. The parts inside the unit may still have hazardous voltage after turning off the UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility power supply.

Suggest charging the batteries for 8 hours before use. After connection, turn the bypass breaker in the ONposition, the UPS will charge the batteries automatically. You can also use the UPS immediately without charging the batteries first, but the backup time may be less than the standard value.

If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be used for calculating the capacity of the UPS, as its start-up power consumption is too big when it is started.

Input and output Terminal Block wiring diagram of 6000L(XL)/10000L(XL)

Important notes: If the UPS is used in single mode, JPI and JP2 must be connected by 10AWG(6mm2). If the UPS is used in parallel mode, the Jumper between JP1 and JP2 must be removed

7

Image 9
Contents Uninterruptible Power Supply Contents Description of commonly used symbols Brief introductionSystem and model description Nation and Explanation AppearancePage Electrical performance Unpacking and inspection InstallationPage Page Option Option Page Parallel operation Operation Operation and Operating modePage Operating mode Function Page RS232 interface GND Battery maintenance Replacement Problem Possible cause Solution TroubleshootingUPS Set the bypass breaker in on position Appendix 1: display panel Appendix 2: The corresponding form of the LED Display Page 614-03753-01