Eaton Electrical 6000L(XL), 10000L(XL) user manual Operation and Operating mode

Page 14

3.Parallel operation

To perform the general operation, follow the stand-alone operating requirement:

1)Startup: The units transfer to INV mode simultaneously as they start up sequentially in utility power mode;

2)Shutdown: the units shut down sequentially in INV mode. When the l ast one completes the shutdown action, each unit will shut down the inverter simultaneously and transfer to bypass mode.

It is easy to operate the equipment, with no previous training. You just need to read through this manual and operate according to the instructions in it. The meaning of the LED indicators, please refer to the appendix 1 Display panel

3.Operation and Operating mode

3.1Operation

1.Turn on the UPS with utility power supplied (in Line mode/AC mode)

1)After you make sure that the power supply connection is correct, set the bypass breaker and the input breaker in the ONposition first. At this time the fan rotates and the UPS supplies power to the load via the bypass. The UPS operates in Bypass mode.

12

Image 14
Contents Uninterruptible Power Supply Contents System and model description Description of commonly used symbolsBrief introduction Appearance Nation and ExplanationPage Electrical performance Installation Unpacking and inspectionPage Page Option Option Page Parallel operation Operation and Operating mode OperationPage Operating mode Function Page RS232 interface GND Battery maintenance Replacement Troubleshooting Problem Possible cause SolutionUPS Set the bypass breaker in on position Appendix 1: display panel Appendix 2: The corresponding form of the LED Display Page 614-03753-01