The voltage or

The UPS is running in battery mode. To

 

frequency of the

save your data and close the application

The utility power

utility power is

program. Make sure the utility power is

LED flashes

out of the input

within the input voltage or frequency

 

range of the

range permitted by the UPS.

 

UPS.

 

The #1 Fault LED

The UPS is

Check the loads and remove all

no-critical equipment. Recalculate the

and the #2 LED are

overloaded or the

load power and reduce the number of

turned on, the UPS

load equipment

loads connected to the UPS. Check that

beeps continuously

is faulty

the loads are not failed.

 

 

22

Image 24
Contents Uninterruptible Power Supply Contents Description of commonly used symbols Brief introductionSystem and model description Appearance Nation and ExplanationPage Electrical performance Installation Unpacking and inspectionPage Page Option Option Page Parallel operation Operation and Operating mode OperationPage Operating mode Function Page RS232 interface GND Battery maintenance Replacement Troubleshooting Problem Possible cause SolutionUPS Set the bypass breaker in on position Appendix 1: display panel Appendix 2: The corresponding form of the LED Display Page 614-03753-01