Advantech EKI-1352, EKI-1351 manual Setting TCP/UDP Server/Client Operating Mode Parameters

Page 44

„Round-Robin mode: Enabling “Response Timeout” parameter, the EKI-1351/ 1352 will operate in “Round-Robin mode”. Each serial port supports up to five simultaneous connections, so multiple hosts can transmit/receive data to/from the same serial port simultaneously. Every host can transmit data to the same serial port simultaneously, but EKI serial device server will process the data communication in order. EKI-1351/1352 will process the first host’s request and

reply the response to the first host. If EKI serial device server receives nothing from serial port after a period of time set by user in "Response Timeout" block, the device server will reply the acknowledgement to the host and then process the next host’s request. The cycle time will be increased when you increase either the number of the connected hosts or the value of "Response Timeout".

„Frame Break is a very import parameter for Round Robin mode. This parameter is a smart way to reduce inefficient waiting time and EKI-1351/1352 can transmit data more efficiently. Disabling the Frame Break function, EKI-1351/1352 will wait for data until "Response Timeout" setting time is reached. During this period, the commands from hosts will be queued and EKI-1351/1352 just processes this command. Enabling “Frame Break”, if the serial port idle is longer than the “Frame Break” period, EKI-1351/1352 will assume the communication is completed and continue the next host’s query. This is an efficient way to reduce the waiting time and improve the performance.

3.4.3Setting TCP/UDP Server/Client Operating Mode Parameters

EKI-1351/1352 provides various operating modes. Selecting the "USDG Mode" as below to change the mode of the port to TCP server/client or UDP mode. Before setting the TCP server mode, you have to check the serial port setting in advance.

EKI-1351/1352 User Manual

38

Image 44
Contents EKI-1351/1352 Product Warranty 2 years Copyright AcknowledgementsSafety Instructions Declaration of ConformityTechnical Support and Assistance FCC Class BSafety Precaution Static Electricity Contents Setting COM Redirector Appendix aChapter Introduction Features SpecificationsPackage Check List Getting Started Understanding EKI-1351/1352 Product DescriptionNormal Mode COM Port Redirector Virtual COM PortMulti-Access Mode Shared COM port mode Multi-Access ModeTCP Server Mode TCP Client ModeControl Mode Serial Tunneling ModeUDP Server/Client Mode LED Indicators HardwareDimensions Units mm EKI-1351 and EKI-1352Back View of EKI-1351/1352 Panel/Wall Mounting Connecting HardwareChoosing the Location DIN Rail Mounting 12 DIN-rail StepWireless Connection Power ConnectionSerial Device Server Configuration Utility Serial ConnectionPage Getting Started Page Configuration Configuration Utility Overview Discovering Serial Device Servers Auto SearchingPage Configuration Clear Device List and Search Again Manual AppendingSetting Ethernet Parameters Ethernet BasicAssociation Information Wireless BasicsWireless Basic Information Wireless Basic Settings Site Survey Wireless Authentication Page Wireless Advanced Beacon IntervalSetting Serial Parameters RTS ThresholdFragment Threshold Preamble TypeSetting Serial Port Parameters Setting Virtual COM Operating Mode Parameters Configuration Setting TCP/UDP Server/Client Operating Mode Parameters Configuration Setting Control Operating Mode Parameters AT Commands List Security Configuration Accessible FunctionFulfilling Administrator Functions Port MonitorImport/Export Serial Port Setting Locate Serial DeviceRestore to Factory Default Settings Lock DeviceUpgrading the Firmware Configuration Page Setting COM Redirector Setting COM RedirectorVirtual COM port Auto MappingSetting COM Redirector Manual Mapping Auto Reconnect Property Manual Direct Mapping Virtual COM Port Remove the Virtual COM PortRunning Diagnostic Test Page Appendix a Diagnostic Ad hoc Mode With wireless moduleDiagnostic Infrastructure Mode Without wireless module