FS-8700-17 Optomux

Driver Manual

4.4.8Map Descriptor Example 5 – Using Address and Length to tell the FieldServer which module positions to access.

This example shows a map descriptor which reads analog inputs from an Optomux Device. The address and length tell the driver which inputs to read. Take care to ensure that the data array used for storage has a data format suitable for storing the data type returned by the command. In this case an unsigned integer at least 16 bits long ( eg UINT16 or FLOAT). Also take care to ensure that you understand the scaling of the data returned by the Optomux device. There are parameters that you can add to a map descriptor to have the driver scale the value. This is discussed in the FieldServer Configuration Manual.

Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Address, Length, Scan_Interval, opto22_function

DEVICE77_STAT , ANA_DATA , 0

, rdbc , DEV77 , 2

, 15 , 1.0s

, READ ANALOG INPUTS

Data read from the Optomux Device is placed in this array.

Starting at this array position.

The first module position that is read is position 2.

Module positions are numbered 1 to 16.

Data from 15 module positions must be read. Thus starting at 2, the last module position read is 16.

This is the Optomux Driver function that must be performed.

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 14

Image 16
Contents FS-8700-17 Optomux Table of Contents Optomux Driver Description Driver Scope of Supply Optomux SystemHardware Connections FS-X40Configuring the FieldServer as a Optomux Driver Client Data ArraysClient Side Connections Client Side NodesClient Side Map Descriptors FieldServer Related Map Descriptor ParametersDriver Related Map Descriptor Parameters Bit, Packed SET Time Delay Generate N Pulses Read and Average Inputs Timing ParametersDEVICE77STAT , Discinputs Map Descriptor Example 1 Read on/off StatusRead Status FS-8700-17 Optomux Driver Manual Map Descriptor Example 3 Command Response/Completion Status Read STATUS, ResponsearrMap Descriptor Example 4 Triggered Action DEVICE77STAT , CntrposnsDEVICE77STAT , Anadata This example, module positions 1 and 5 are pulsed PULSE77 TimedataCLRLOW77 Lowarray Wrbc , DEV77 , 16 , 10.0sConfiguring the FieldServer as a Optomux Server Command Response Status Driver NotesDataArrayName, DABitName, DAByteName Module PositionsOptomux Commands FS-8700-17 Optomux Driver Manual Read Specified module positions get set Affected. The data period of pulses Only one module position may be Calculated and read. Data read gets Array Element Contents Driver StatsRevision History