4 Configuring the FieldServer as a Optomux Driver Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with an Optomux Device.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Optomux Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1 Data Arrays

Section Title

 

 

Data_Arrays

 

 

Column Title

Function

Legal Values

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric

 

 

characters

Data_Format

Provide data format. Each data array can

FLOAT, BIT, UInt16, SInt16,

 

only take on one format.

Packed_Bit, Byte,

 

 

Packed_Byte,

 

 

Swapped_Byte

Data_Array_Length

Number of Data Objects. Must be larger

1-10,000

 

than the data storage area required for

 

 

the data being placed in this array.

 

 

 

 

Example

//Data Arrays

Data_Arrays

Data_Array_Name, Data_Format, Data_Array_Length

DA_AI_01,

UInt16,

200

DA_AO_01,

UInt16,

200

DA_DI_01,

Bit,

200

DA_DO_01,

Bit,

200

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 4

Image 6
Contents FS-8700-17 Optomux Table of Contents Optomux Driver Description Driver Scope of Supply Optomux SystemHardware Connections FS-X40Configuring the FieldServer as a Optomux Driver Client Data ArraysClient Side Connections Client Side NodesClient Side Map Descriptors FieldServer Related Map Descriptor ParametersDriver Related Map Descriptor Parameters Bit, Packed SET Time Delay Generate N Pulses Read and Average Inputs Timing ParametersMap Descriptor Example 1 Read on/off Status DEVICE77STAT , DiscinputsRead Status FS-8700-17 Optomux Driver Manual Map Descriptor Example 3 Command Response/Completion Status Read STATUS, ResponsearrMap Descriptor Example 4 Triggered Action DEVICE77STAT , CntrposnsDEVICE77STAT , Anadata This example, module positions 1 and 5 are pulsed PULSE77 TimedataCLRLOW77 Lowarray Wrbc , DEV77 , 16 , 10.0sConfiguring the FieldServer as a Optomux Server DataArrayName, DABitName, DAByteName Command Response StatusDriver Notes Module PositionsOptomux Commands FS-8700-17 Optomux Driver Manual Read Specified module positions get set Affected. The data period of pulses Only one module position may be Calculated and read. Data read gets Array Element Contents Driver StatsRevision History