Driver Manual |
4.2Client Side Connections
Section Title |
|
|
Connections |
|
|
Column Title | Function | Legal Values |
Port | Specify which port the device is | |
| connected to the FieldServer | R1 |
Baud* | Specify baud rate | 110 – 115200, standard baud |
|
| rates only |
|
| At the time of publication of this |
|
| manual the OPTO22 device’s |
|
| support standard baud Rates in |
|
| the range |
Parity* | Specify parity | Even, Odd, None, Mark, Space |
Data_Bits* | Specify data bits | 7, 8 |
Stop_Bits* | Specify stop bits | 1 |
Protocol | Specify protocol used | Optomux |
|
|
|
Handshaking* | Specify hardware handshaking | RTS, RTS/CTS, None |
Poll Delay* | Time between internal polls | |
|
| default 1 second |
Example |
|
|
//Client Side Connections
Connections
Port, Baud, Parity, Protocol, Handshaking, Poll_Delay
R1, 9600, None, Opto22 , None | , 0.100s |
4.3 Client Side Nodes
Section Title |
|
|
Nodes |
|
|
Column Title | Function | Legal Values |
Node_Name | Provide name for node | Up to 32 alphanumeric |
|
| characters |
Node_ID | OPTO22 device address. | |
Protocol | Specify protocol used | Optomux |
Port | Specify which port the device is | |
| connected to the FieldServer | converter) |
Example
//Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
Optomux1 , 1 , Optomux , R1
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408)
Visit our website: www.fieldserver.com
Page 5