FieldServer FS-8700-17 instruction manual Affected. The data period of pulses

Page 24

 

FS-8700-17 Optomux

 

 

Driver Manual

Read/

COMMAND NAME

OPTO22_FORMAT

MASTER LENGTH

NOTES

Write/

 

OPTION

CONSIDERED (See

 

Both

 

 

Notes)

 

 

 

 

 

affected. The Modifier (byte 1&2) are specified in the CSV file with the opto22_modifier1/2 parameters. The data (number of pulses) is retrieved from the 1st element of the data array.

w

START ON PULSE

 

3

Only specified module positions get

 

 

 

 

affected. The data (period of pulses)

 

 

 

 

is retrieved from the 1st element of

 

 

 

 

the data array.

w

START OFF PULSE

 

3

Only specified module positions get

 

 

 

 

affected. The data (period of pulses)

 

 

 

 

is retrieved from the first element of

 

 

 

 

the data array.

w

SET TRIGGER POLARITY

 

3

All Module positions are affected by

 

 

 

 

this command. Non-zero (Specified)

 

 

 

 

module positions triggered by on,

 

 

 

 

zero module positions (un-specified)

 

 

 

 

elements get triggered by off.

w

TRIGGER ON POSITIVE

 

3

Only module positions specified get

 

 

 

 

affected by command.

w

TRIGGER ON NEGATIVE

 

3

Only module positions specified get

 

 

 

 

affected by command.

r

READ PULSE COMPLETE BITS

1

2

If format=Bit then length is considered

 

 

 

 

during storage as bits are unpacked

 

 

 

 

into data array. If format is non equal

 

 

 

 

to bit then result is written as a single

 

 

 

 

value into one array element.

 

 

 

 

Retrieved data is stored in standard

 

 

 

 

data array.

r

READ DURATION COUNTERS

 

3

Only specified module positions get

 

 

 

 

read. Data read gets put in

 

 

 

 

corresponding positions of data array.

b

READ AND CLEAR DURATION

 

3

Only specified module positions get

 

COUNTERS

 

 

read. Data read gets put in

 

 

 

 

corresponding positions of data array.

w

CLEAR DURATION COUNTERS

 

3

Only module positions specified get

 

 

 

 

affected by command.

w

WRITE ANALOG OUTPUTS

 

3

Only specified module positions get

 

 

 

 

written. Data written gets extracted

 

 

 

 

from corresponding positions of data

 

 

 

 

array.

r

READ ANALOG OUTPUTS

 

3

Only specified module positions get

 

 

 

 

read. Data read gets put in

 

 

 

 

corresponding positions of data array.

w

UPDATE ANALOG OUTPUTS

 

3

Only specified module positions get

 

 

 

 

written. Data written gets extracted

 

 

 

 

from corresponding positions of data

 

 

 

 

array.

r

READ ANALOG INPUTS

 

3

Only specified module positions get

 

 

 

 

read. Data read gets put in

 

 

 

 

corresponding positions of data array.

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 22

Image 24
Contents FS-8700-17 Optomux Table of Contents Optomux Driver Description Driver Scope of Supply Optomux SystemHardware Connections FS-X40Configuring the FieldServer as a Optomux Driver Client Data ArraysClient Side Connections Client Side NodesClient Side Map Descriptors FieldServer Related Map Descriptor ParametersDriver Related Map Descriptor Parameters Bit, Packed SET Time Delay Generate N Pulses Read and Average Inputs Timing ParametersMap Descriptor Example 1 Read on/off Status DEVICE77STAT , DiscinputsRead Status FS-8700-17 Optomux Driver Manual Map Descriptor Example 3 Command Response/Completion Status Read STATUS, ResponsearrMap Descriptor Example 4 Triggered Action DEVICE77STAT , CntrposnsDEVICE77STAT , Anadata This example, module positions 1 and 5 are pulsed PULSE77 TimedataCLRLOW77 Lowarray Wrbc , DEV77 , 16 , 10.0sConfiguring the FieldServer as a Optomux Server Command Response Status Driver NotesDataArrayName, DABitName, DAByteName Module PositionsOptomux Commands FS-8700-17 Optomux Driver Manual Read Specified module positions get set Affected. The data period of pulses Only one module position may be Calculated and read. Data read gets Array Element Contents Driver StatsRevision History