4.4.7.Map Descriptor Example 4 - Analog Output 1 (Area Machine)

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on the Lutron eLumen panel. Scenes range from 0 to 65535 and area numbers range from 0 to 511

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD000_AO,

Analog_Output,

0,

Server,

Virtual_BCU_11,

AO,

1,

512,

0

Lutron Machine Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Grafik_Command,

area,

Length

Sel_scene_0,

Analog_Output,

0,

AWT,

LUT_GRF6_0,

sel_scene_in_area,

0,

512

The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified under Data_Array_Name. Area numbers increase with the Length field in association with increasing offset into the Data Array.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 14
Contents FS-8700-97 Lutron Machine Effective for all systems manufactured after May 1Table of Contents FS-8700-97LutronMachine Manual Max Nodes Supported FieldServer Mode CommentsLutron Machine Description Required 3rd Party Software Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware FieldServer Technologies DescriptionHardware Connections FS-B2010FS-8700-97LutronMachine Manual Section Title Configuring the FieldServer as a Lutron Machine ClientData Arrays/Descriptors Column Title Function Legal ValuesClient Side Connection Descriptions Client Side Node Descriptors Driver Related Map Descriptor ParametersTiming Parameters BACnet IP Map Descriptor Lutron Machine Map DescriptorMap Descriptor Example 2 Binary Input Zone Machine Lutron Machine Map DescriptorMap Descriptor Example 3 Binary Input Area Machine Map Descriptor Example 4 Analog Output 1 Area Machine Map Descriptor Example 5 Analog Output 1 Zone Machine Runscriptmulti ScrlstAO2512 FS-8700-97LutronMachine Manual Map Descriptor Example 7 Analog Input Area Machine Map Descriptor Example 8 Analog Input Zone Machine SMD00MO FS-8700-97LutronMachine Manual Map Descriptor Example 10 Binary Value Zone and Area Machine Map Descriptor Example 11 Analog Value Zone and Area Machine Appendix A. Revision History Date Resp Format Driver Doc Comment Ver