FieldServer FS-8700-97 instruction manual Map Descriptor Example 8 Analog Input Zone Machine

Page 19

FS-8700-97_Lutron_Machine Manual

Page 19 of 24

4.4.11.Map Descriptor Example 8 - Analog Input (Zone Machine)

A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the intensity to which a given zone is set on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the zone intensities. The intensity value returned is scaled to a percentage value (0 to 100%). Zone numbers range from 0 to 511.

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD00_AI,

Analog_Input,

0,

Server,

Virtual_BCU_11,

AI,

1,

512,

0

Lutron Machine Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

 

Node_name,

 

Grafik_Command,

zone,

Length

Zone_inta_0,

Analog_Input,

0,

ARCO,

 

LUT_GRF6_0,

 

zone_intensity,

0,

512

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The start zone number is specified under the “zone” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC Map Descriptors with the same length.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 19
Contents Effective for all systems manufactured after May 1 FS-8700-97 Lutron MachineTable of Contents Lutron Machine Description Max Nodes Supported FieldServer Mode CommentsFS-8700-97LutronMachine Manual FieldServer Technologies Description Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware Required 3rd Party SoftwareFS-B2010 Hardware ConnectionsFS-8700-97LutronMachine Manual Column Title Function Legal Values Configuring the FieldServer as a Lutron Machine ClientData Arrays/Descriptors Section TitleClient Side Connection Descriptions Driver Related Map Descriptor Parameters Client Side Node DescriptorsTiming Parameters Lutron Machine Map Descriptor BACnet IP Map DescriptorLutron Machine Map Descriptor Map Descriptor Example 2 Binary Input Zone MachineMap Descriptor Example 3 Binary Input Area Machine Map Descriptor Example 4 Analog Output 1 Area Machine Map Descriptor Example 5 Analog Output 1 Zone Machine Runscriptmulti ScrlstAO2512 FS-8700-97LutronMachine Manual Map Descriptor Example 7 Analog Input Area Machine Map Descriptor Example 8 Analog Input Zone Machine SMD00MO FS-8700-97LutronMachine Manual Map Descriptor Example 10 Binary Value Zone and Area Machine Map Descriptor Example 11 Analog Value Zone and Area Machine Date Resp Format Driver Doc Comment Ver Appendix A. Revision History