4.Configuring the FieldServer as a Lutron Machine Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer instruction manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Lutron eLumen panel.

4.1.Data Arrays/Descriptors

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Lutron Machine communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

 

 

Data_Arrays

 

 

 

 

 

Column Title

Function

 

Legal Values

 

Data_Array_Name

Provide name for Data Array

 

Up to 15

alphanumeric

 

 

characters

 

 

 

 

 

 

 

 

 

 

Float, Bit, UInt16, SInt16,

 

Data_Array_Format

Provide data format. Each

Data

Packed_Bit,

Byte,

 

Array can only take on one format.

Packed_Byte,

 

 

 

 

 

 

Swapped_Byte

 

 

Number of Data Objects. Must be

 

 

 

Data_Array_Length

larger than the data storage area

1-10,000

 

 

required by the Map Descriptors for

 

 

 

the data being placed in this array.

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

 

Data_Arrays

 

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

Binary_Output,

Bit,

512

 

 

Binary_Input,

Bit,

512

 

 

Analog_Output,

Uint16,

512

 

 

Analog_Input,

Uint16,

512

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 7
Contents Effective for all systems manufactured after May 1 FS-8700-97 Lutron MachineTable of Contents Lutron Machine Description Max Nodes Supported FieldServer Mode CommentsFS-8700-97LutronMachine Manual FieldServer Technologies Description Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware Required 3rd Party SoftwareFS-B2010 Hardware ConnectionsFS-8700-97LutronMachine Manual Column Title Function Legal Values Configuring the FieldServer as a Lutron Machine ClientData Arrays/Descriptors Section TitleClient Side Connection Descriptions Driver Related Map Descriptor Parameters Client Side Node DescriptorsTiming Parameters Lutron Machine Map Descriptor BACnet IP Map DescriptorLutron Machine Map Descriptor Map Descriptor Example 2 Binary Input Zone MachineMap Descriptor Example 3 Binary Input Area Machine Map Descriptor Example 4 Analog Output 1 Area Machine Map Descriptor Example 5 Analog Output 1 Zone Machine Runscriptmulti ScrlstAO2512 FS-8700-97LutronMachine Manual Map Descriptor Example 7 Analog Input Area Machine Map Descriptor Example 8 Analog Input Zone Machine SMD00MO FS-8700-97LutronMachine Manual Map Descriptor Example 10 Binary Value Zone and Area Machine Map Descriptor Example 11 Analog Value Zone and Area Machine Date Resp Format Driver Doc Comment Ver Appendix A. Revision History