FieldServer FS-8700-97 Map Descriptor Example 10 Binary Value Zone and Area Machine

Page 22

FS-8700-97_Lutron_Machine Manual

Page 22 of 24

4.4.13.Map Descriptor Example 10 - Binary Value (Zone and Area Machine)

A read from the Binary Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system variable in the Lutron eLumen panel. The value returned is inactive (0) if the system variable is zero and active (1) if non-zero. The Lutron Machine Map Descriptor regularly polls the Lutron panel to retrieve the system variable values. A write to the Binary Value Data Array will set the system variable to 255 on active (1) write or to zero on inactive (0) write.

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD00_BV,

Binary_Value,

0,

Server,

Virtual_BCU_11,

BV,

1,

512,

0

Lutron Machine Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Grafik_Command,

Sys_Var,

Length

Zone_var_0,

Binary_Value,

0,

ARCO,

LUT_GRF6_0,

sys_var_val_bin,

0,

512

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of system variables to poll. The start system variable number is specified under the “Sys_Var” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two series of system variable numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC Map Descriptors with the same length.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 22
Contents FS-8700-97 Lutron Machine Effective for all systems manufactured after May 1Table of Contents Lutron Machine Description Max Nodes Supported FieldServer Mode CommentsFS-8700-97LutronMachine Manual Required 3rd Party Software Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware FieldServer Technologies DescriptionHardware Connections FS-B2010FS-8700-97LutronMachine Manual Section Title Configuring the FieldServer as a Lutron Machine ClientData Arrays/Descriptors Column Title Function Legal ValuesClient Side Connection Descriptions Client Side Node Descriptors Driver Related Map Descriptor ParametersTiming Parameters BACnet IP Map Descriptor Lutron Machine Map DescriptorMap Descriptor Example 2 Binary Input Zone Machine Lutron Machine Map DescriptorMap Descriptor Example 3 Binary Input Area Machine Map Descriptor Example 4 Analog Output 1 Area Machine Map Descriptor Example 5 Analog Output 1 Zone Machine Runscriptmulti ScrlstAO2512 FS-8700-97LutronMachine Manual Map Descriptor Example 7 Analog Input Area Machine Map Descriptor Example 8 Analog Input Zone Machine SMD00MO FS-8700-97LutronMachine Manual Map Descriptor Example 10 Binary Value Zone and Area Machine Map Descriptor Example 11 Analog Value Zone and Area Machine Appendix A. Revision History Date Resp Format Driver Doc Comment Ver