4.4.14.Map Descriptor Example 11 - Analog Value (Zone and Area Machine)

A read from the Analog Value Data Array which is shared by a BACNet IP Map Descriptor will return the current value of a system variable in the Lutron eLumen panel. The variable values range from 0 to 255. The Lutron Machine Map Descriptors are regularly updated with system variable values from the active Binary Value Map Descriptors. A write to the Analog Value Data Array will set the system variable to the written value.

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD00_AV,

Analog_Value,

0,

Server,

Virtual_BCU_11,

AV,

1,

512,

0

Lutron Machine Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

 

Node_name,

 

Grafik_Command,

Sys_Var,

Length

Zone_vara_0,

Analog_Value,

0,

Passive_Client,

 

LUT_GRF6_0,

 

sys_var_val,

0,

512

The Passive_Client function is used to prevent double-polling the Lutron eLumen panel for system variables. The Analog Value Map Descriptors should be set up identical to the Binary Value Map Descriptors in terms of the Sys_Var and Length fields to ensure system variable values will be stored correctly.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 23
Contents Effective for all systems manufactured after May 1 FS-8700-97 Lutron MachineTable of Contents FS-8700-97LutronMachine Manual Max Nodes Supported FieldServer Mode CommentsLutron Machine Description FieldServer Technologies Description Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware Required 3rd Party SoftwareFS-B2010 Hardware ConnectionsFS-8700-97LutronMachine Manual Column Title Function Legal Values Configuring the FieldServer as a Lutron Machine ClientData Arrays/Descriptors Section TitleClient Side Connection Descriptions Driver Related Map Descriptor Parameters Client Side Node DescriptorsTiming Parameters Lutron Machine Map Descriptor BACnet IP Map DescriptorLutron Machine Map Descriptor Map Descriptor Example 2 Binary Input Zone MachineMap Descriptor Example 3 Binary Input Area Machine Map Descriptor Example 4 Analog Output 1 Area Machine Map Descriptor Example 5 Analog Output 1 Zone Machine Runscriptmulti ScrlstAO2512 FS-8700-97LutronMachine Manual Map Descriptor Example 7 Analog Input Area Machine Map Descriptor Example 8 Analog Input Zone Machine SMD00MO FS-8700-97LutronMachine Manual Map Descriptor Example 10 Binary Value Zone and Area Machine Map Descriptor Example 11 Analog Value Zone and Area Machine Date Resp Format Driver Doc Comment Ver Appendix A. Revision History