FieldServer FS-8700-97 instruction manual Map Descriptor Example 5 Analog Output 1 Zone Machine

Page 15

FS-8700-97_Lutron_Machine Manual

Page 15 of 24

4.4.8.Map Descriptor Example 5 - Analog Output 1 (Zone Machine)

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command a zone on the Lutron eLumen panel to the written intensity. Intensities are written as a percentage value (0 to 100%).

BACNet IP Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD000_AO,

Analog_Output,

0,

Server,

Virtual_BCU_11,

AO,

1,

512,

0

Lutron Machine Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Grafik_Command,

zone,

DA_Lut_Parms,

DA_Lut_Parms_Offset,

Length

Fade_to_lvl_0,

Analog_Output,

0,

AWT,

LUT_GRF6_0,

fade_zone,

0,

Zone_pars_AO1,

0,

512

The zone field must be used to indicate the start zone number that will be associated with the first element of the Data Array specified under Data_Array_Name . Zone numbers increase with the Length field in association with increasing offset into the Data Array.

Fade and Delay times per zone must be preloaded into the Data Array specified under “DA_Lut_Parms”: //================================================================================

//Analog Output1 Settings Setup

//All values are in decimal ( 0 - 65535 )

//Fade time in even locations, Delay time in uneven locations

//Fill in time values under Preload_Data_Value

 

Preloads

 

 

 

 

 

 

 

 

 

Data_Array_Name ,

Preload_Data_Format ,

Preload_Data_Value ,

Location

 

// Analog Output1 Object ID 1

Uint16

,

 

0

,

 

0

 

 

Zone_pars_AO1 ,

 

 

 

 

Zone_pars_AO1 ,

 

Uint16

,

 

1

,

 

1

 

 

// Analog Output1 Object ID 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone_pars_AO1 ,

 

Uint16

,

 

2

,

 

2

 

 

Zone_pars_AO1 ,

 

Uint16

,

 

3

,

 

3

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 15
Contents Effective for all systems manufactured after May 1 FS-8700-97 Lutron MachineTable of Contents Max Nodes Supported FieldServer Mode Comments Lutron Machine DescriptionFS-8700-97LutronMachine Manual FieldServer Technologies Description Required 3rd Party ConfigurationProvided by the Supplier of 3rd Party Equipment Hardware Required 3rd Party SoftwareFS-B2010 Hardware ConnectionsFS-8700-97LutronMachine Manual Column Title Function Legal Values Configuring the FieldServer as a Lutron Machine ClientData Arrays/Descriptors Section TitleClient Side Connection Descriptions Driver Related Map Descriptor Parameters Client Side Node DescriptorsTiming Parameters Lutron Machine Map Descriptor BACnet IP Map DescriptorLutron Machine Map Descriptor Map Descriptor Example 2 Binary Input Zone MachineMap Descriptor Example 3 Binary Input Area Machine Map Descriptor Example 4 Analog Output 1 Area Machine Map Descriptor Example 5 Analog Output 1 Zone Machine Runscriptmulti ScrlstAO2512 FS-8700-97LutronMachine Manual Map Descriptor Example 7 Analog Input Area Machine Map Descriptor Example 8 Analog Input Zone Machine SMD00MO FS-8700-97LutronMachine Manual Map Descriptor Example 10 Binary Value Zone and Area Machine Map Descriptor Example 11 Analog Value Zone and Area Machine Date Resp Format Driver Doc Comment Ver Appendix A. Revision History