| Marathon Monitors Inc. |
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Two terminal modules |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
Note: | Module 1 is connected to terminals 1A and 1B |
|
| ||||||||||||||||||||
|
| Module 2 is connected to terminals 2A and 2B |
|
| |||||||||||||||||||
|
| Module 3 is connected to terminals 3A and 3B. |
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Terminal identity |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Module type |
|
|
| A |
|
|
| B | C |
| D |
| Possible functions | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Relay: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Unused |
| Heating, cooling, alarm, | ||
| (2A, 264 Vac max.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| program event, valve raise, | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| or valve lower | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Logic - | + |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Unused |
| Heating, cooling, mode 1, | ||||
| (18Vdc at 20mA) |
|
|
|
|
|
|
|
|
|
|
| − |
|
|
|
| mode 2, program event | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Triac |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Unused |
| Heating, cooling, program | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| (1A, 30 to 264Vac) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| event, valve raise, or valve | ||
|
| Line |
|
|
| Load |
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
| lower | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| DC output: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Unused |
| Heating, or cooling, or | ||
|
| + |
|
|
|
|
|
|
| − |
|
| |||||||||||
|
| - |
|
|
|
|
|
|
|
|
|
|
| retransmission of PV, | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| (10Vdc, 20mA max.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| setpoint, or control output | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table
Snubbers
The relay and triac modules have an internal 15nF/100Ω ‘snubber’ connected across their output, which is used to prolong contact life and to suppress interference when switching inductive loads, such as mechanical contactors and solenoid valves.
WARNING
When the relay contact is open, or the triac is off, the snubber circuit passes 0.6mA at 110Vac and 1.2mA at 240Vac. You must ensure that this current, passing through the snubber, will not hold on low power electrical loads. It is your responsibility as the installer to ensure that this does not happen. If the snubber circuit is not required, it can be removed from the relay module (BUT NOT THE TRIAC) by breaking the PCB track that runs crosswise, adjacent to the edge connectors of the module. This can be done by inserting the blade of a small screwdriver into one of the two slots that bound it, and twisting.
AACC 2000 Carbon | 17 | Nov. 1, 1997 |
|
|