Marathon Monitors Inc.
Linear Input Scaling − The next 4 parameters only appear if a linear or sq rt input is chosen.
inp.L | Displayed Value |
|
| Input value low |
inp.H | VAL. H |
|
| Input value high |
|
|
| ||
VAL.L |
|
|
| Displayed reading low |
VAL.H | VAL. L |
| Electrical | Displayed reading high |
|
| |||
inP.L | inP.H | Input |
Name | Description | Values | Meaning |
|
|
|
|
SP | Setpoint configuration |
|
|
nSP | Number of setpoints | 2, 4, 16 | Select number of setpoints available |
rm.tr | Remote Tracking | OFF | Disable |
|
| trAc | Local setpoint tracks remote setpoint |
m.tr | Manual Track | OFF | Disable |
|
| trAc | Local setpoint tracks PV when in |
|
|
| manual |
rmP.U | Setpoint rate limit units | PSEc | Per second |
|
| Pmin | Per minute |
|
| PHr | Per hour |
rmt | Remote setpoint configuration | nonE | Disable |
|
| SP | Remote setpoint |
|
| Loc.t | Remote setpoint + local trim |
|
| rmt.t | Remote trim + local setpoint |
AACC 2000 Carbon | 72 | Nov. 1, 1997 |