Marathon Monitors Inc.
Integral action and manual reset
In a full
Automatic droop compensation (Adc)
The steady state error from the setpoint, which occurs when the integral term is set to ‘OFF’ is sometimes referred to as ‘droop’. ‘Adc’ automatically calculates the manual reset value in order to remove this droop. To use this facility, you must first allow the process variable to stabilise. Then, in the autotune parameter list, you must set ‘Adc’ to
‘on’. The controller will then calculate a new value for manual reset, and switch ‘Adc’ to ‘OFF’.
‘Adc’ can be repeated as often as you require, but between each adjustment you must allow time for the process variable to stabilise.