| Marathon Monitors Inc. | |
|
| |
Technical Specification | ||
Environmental ratings |
|
|
Panel sealing: | Instruments are intended to be panel mounted. The | |
| rating of panel sealing is IP65, (EN 60529), or 4X, (NEMA | |
| 250). |
|
Operating temperature: | 0 to 55oC. Ensure the enclosure provides adequate | |
ventilation. |
|
|
Relative humidity: | 5 to 95%, non condensing. | |
Atmosphere: | The instrument is not suitable for use above 2000m | |
| or in explosive or corrosive atmospheres. | |
Equipment ratings |
|
|
Supply voltage: | 100 to 240Vac | |
Supply frequency: | 48 to 62Hz. | |
Power consumption: | 15 Watts maximum. | |
Relay | Maximum: 264Vac, 2A resistive. Minimum: 12Vdc, 100mA. | |
Relay changeover (isolated): Maximum: 264Vac, 2A resistive. Minimum: 6Vdc, 1mA. | ||
Triac outputs (isolated): | 30 to 264Vac. Maximum current: 1A resistive. | |
Leakage current: | The leakage current through triac and relay contact | |
| suppression components is less than 2mA at 264Vac, 50Hz. | |
Over current protection: | External over current protection devices are required that | |
| match the wiring of the installation. A minimum of 0.5mm2 or | |
| 16awg wire is recommended. Use independent fuses for the | |
| instrument supply and each relay or triac output. Suitable | |
| fuses are T type, (EN 60127 | |
| Instrument supply: 85 to 264Vac, 2A, (T). | |
| Relay outputs: 2A (T). Triac outputs: 1A (T). | |
Low level i/o: | All input and output connections other than triac and relay are | |
| intended for low level signals less than 42V. | |
Single logic output: | 18V at 24mA. | |
DC output (Isolated): | 0 to 20mA (600Ω max), 0 to 10V (500Ω min). | |
DC output (Non isolated): | 0 to 20mA (600Ω max), 0 to 10V (500Ω min). | |
Fixed digital inputs: | Contact closure. (Non isolated.) | |
Triple contact input: | Contact closure. (Isolated.) | |
Triple logic input: | 11 to 30Vdc. (Isolated.) | |
DC or 2nd PV input: | As main input plus | |
| (Isolated.) | |
Potentiometer input: | 0.5V excitation, 100Ω to 1.5kΩ Potentiometer. (Isolated.) | |
Transmitter supply: | 24Vdc at 20mA. (isolated.) | |
Strain gauge supply: | 10Vdc. Minimum bridge resistance 300Ω. (Isolated.) | |
Digital Communications: |
AACC 2000 Carbon | 8 | Nov. 1, 1997 |
|
|