Marathon Computer AACC 2000 manual Safety Symbols, Personnel, Enclosure of live parts, Wiring

Page 5

Marathon Monitors Inc.

Installation Safety Requirements

Safety Symbols

Various symbols are used on the instrument, they have the following meaning:

Caution, (refer to the

! accompanying documents)

Functional earth (ground) terminal

The functional earth connection is not required for safety purposes but to ground RFI filters.

Personnel

Installation must only be carried out by qualified personnel.

Enclosure of live parts

To prevent hands or metal tools touching parts that may be electrically live, the controller must be installed in an enclosure.

Caution: Live sensors

The fixed digital inputs, non-isolated dc, logic and outputs and the logic output of dual output modules, are all electrically connected to the main process variable input. If the temperature sensor is connected directly to an electrical heating element then these non- isolated inputs and outputs will also be live. The controller is designed to operate under these conditions. However you must ensure that this will not damage other equipment connected to these inputs and outputs and that service personnel do not touch connections to these i/o while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs and outputs must be mains rated.

Wiring

It is important to connect the controller in accordance with the wiring data given in this handbook. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections (except thermocouple inputs) and ensure that the wiring of installations comply with all local wiring regulations. For example in the in the UK use the latest version of the IEE wiring regulations, (BS7671). In the USA use NEC Class 1 wiring methods.

Power Isolation

The installation must include a power isolating switch or circuit breaker. This device should be in close proximity to the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.

Earth leakage current

Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the design of an installation of multiple controllers protected by Residual Current Device, (RCD) or Ground Fault Detector, (GFD) type circuit breakers.

AACC 2000 Carbon

5

Nov. 1, 1997

 

 

Image 5
Contents Copyright Marathon Monitors INC Marathon Monitors Inc Mechanical Installation Electrostatic discharge precautions SafetyCleaning Electromagnetic compatibilityWiring Safety SymbolsPower Isolation PersonnelOvercurrent protection Over-temperature protectionVoltage rating Conductive pollutionRouting of wires Installation requirements for EMCGrounding of the temperature sensor shield Equipment ratings Environmental ratingsGeneral Electrical safetyMarathon Monitors Inc Installation Outline dimensions Model 2000 controller Outline dimensions ModelIntroduction To install the controllerController labels Unplugging and plugging-in the controllerModel Aacc 2000 rear terminal layout Rear terminal layoutsMarathon Monitors Inc Module 1, 2 Sensor input connectionsSnubbers Two terminal modulesDual output modules Four terminal modulesCOM Connections for Process Value 2 PV2 Connections for Process Value 3 in module positionCommunication module EIA-485 wiring Wiring of 2-wire EIA-485 serial communications linkMarathon Monitors Inc Operation Front Panel LAYOUTs 26.0OP1 Button or Name ExplanationOP2 SP2Basic operation AlarmsOperating modes Output power demand Automatic modeHome display Display unitsSetpoint Manual ModeList header displays Parameters and HOW to Access ThemMarathon Monitors Inc To change the value of a parameter Parameter namesParameter displays OFF List1OFF PID.1 PIDSTD FactPass Hydrogen or CO constant Name Description Prob Probe list Process FactorMillivolt input Offset Name Description DrA TunEDrA.t AdcSEt Pid PID listRES HcbInput list Setpoint listInFo Information list Output listCmS Comms list FF.OP Access ListAlarms Display What it means What to do about it Shows Diagnostic alarms2b Diagnostic alarms Access Levels Access to Read-only Configuration Access list headerPassword entry Level selection Configuration passwordConfiguration level Edit level Setting operator access to a parameterReturning to Operator Level Hiding or revealing a complete listPromoting a parameter This sheet intentionally left blank Parameter Code Meaning or Function TuningHow to tune One-shot TuningAdaptive tune Typical automatic tuning cycleCalculation of the cutback values Manual Tuning Proceed as follows Setting the cutback valuesAutomatic droop compensation Adc Integral action and manual resetMotorized valve control Name Description Values Mtr Motor list Min Max DefaultInertia and backlash settings Adjusting the minimum on-time ‘mp.t’Marathon Monitors Inc Set the transfer point Enable in configuration levelGain scheduling Configuration Press to enter configuration Selecting configuration levelChanging the passwords Leaving Configuration LevelLIN REUD1SA Enab SB.OPNone RelyCMS YES DIGPMV Name Description Values Meaning InSt Instrument configurationH2O SP.FFCJC Process value configInput configuration VAL.H Setpoint configurationVAL.L Alarm Modes Alarm configuration ValuesTable a Alarm types Value IMP Digital input 1 configuration Action on contact closureDigital input 2 configuration Action on contact closure Pflt Alarm relay configurationVflt Combining several digital events on to one output Comms 1 module configCool Module config1A b C1 Module 1 configuration For ‘id’ = ‘LoG.i’ i.e logic input use the LA Conf’ list on 2A/b/C Module 2 configurationDisplayed value low SEL 3A/b/C Module 3 configurationModule configuration C Module configurationVAL.8 Point Custom LinearisationVAL.1 CAL Exit Exit configuration Password configurationDC Output Calibration User calibrationUser calibration Calibration Configuration List User Calibration EnableUser Calibration Enable Exit configurationCalibration type Offset calibrationInput list header Set Offset See table on the right for additional parametersDisplayed Value Two-point calibrationSelect Low-point Calibration Adjust low-point calibrationSelect High-point Calibration Adjust High-point CalibrationName Parameter description Meaning Calibration points and Calibration offsetsParameter Table Default HY1 Ssel FLT3 Marathon Monitors Inc AL1 Module 2A High Value VAL.1 101 Index Two-point calibration User calibration Aacc 2000 Carbon