Minuteman UPS MCP 10001, MCP 6001 user manual Inverter Mode

Page 14

3. DISPLAYS AND ALARMS

1.Load level and battery capacity is represented by 5 LEDs on the upper half of control panel (the 6th LED means FAULT).

(A). When the UPS is in the On-Line mode, the 5 LEDs represent load level. They denote 0%~35%, 35%~55%, 55%~75%, 75%~95% and 95%~105% (from buttom to top) of maximum load capacity. If the load amount reaches 105%~130%, the UPS is in overload such that the 6 LEDs would illuminate simultaneously. The UPS will then switch to BYPASS mode10 seconds later. In addition, if the load is over 130%, the UPS will switch to BYPASS immediately.

Figure 3.1-1 Inverter Mode

Figure 3.1-2 Bypass Mode

(B). During an AC line power failure, these 5 LEDs represent the remaining battery capacity. The LED’s will extinguish by the sequence from bottom to top as the battery voltage level decreases.

Figure 3.1-3 Battery Mode

2. An alarm will sound continuously during inverter short-circuiting or an output overvoltage condition.

Figure 3.2-1 Line Mode

Figure 3.2-2 Battery Mode

3. An alarm will sound continuously during a bus overvoltage condition.

Figure 3.3-1 Line Mode

Figure 3.3-2 Battery Mode

Page A2

Image 14
Contents Continuous Power Series User’s Manual MCP Table of Contents System Description Explanation of SymbolsIntroduction Input Product Specifications Electrical SpecificationsMechanical Specifications OutputSwitches and Displays Important Safety Instructions Para Systems Life Support PolicyHazardous Voltage Communication Port Installation and OperationInstallation RS-232 IinterfaceWiring Description Rear ViewOutput Voltage Configurations Output Configuration #5 = 240VAC Obtaining Service TroubleshootingTroubleshooting Chart Minuteman UPSApplication Notes START-UP1 Inverter Mode 1 Bypass Mode Bypass Short Alarm Limited Product Warranty Declaration of Conformity Page 34000139 Rev