Minuteman UPS MCP 10001, MCP 6001 user manual Bypass Short Alarm

Page 16

7. Alarm for abnormal input voltage.

A)During Start-up, the Line LED will flash if the input voltage drops below 185V or above 261V. Pressing the “” button will not switch the UPS from Bypass Mode to Inverter Mode.

(B)During operation, the UPS will switch from Inverter Mode to Battery Mode if the input voltage drops below 170V or above 276V.

(C) In Battery Mode, the UPS does not change mode even if the line power recovers when voltage is below 170V or above 276V. If voltage is between 185V and 261V, the UPS will switch back to Line Mode.

Figure 3.7-1 Bypass Mode

Figure 3.7-2 Battery Mode

8. Battery Mode over-voltage alarm.

When the battery voltage exceeds 300V, the alarm will sound continuously and show the display below:

Figure 3.8-1 Bypass Mode

Figure 3.8-2 Inverter Mode

NOTE: In Battery Mode, the batteries are discharging, hence no alarm sounds.

9. Bypass STS short alarm.

The system will detect if the bypass STS gets shorted when the line breaker is turned on. If the STS short is detected, the display shows as below and the alarm sounds continuously.

Figure 3.9 Bypass Short Alarm

Page A4

Image 16
Contents Continuous Power Series User’s Manual MCP Table of Contents Introduction Explanation of SymbolsSystem Description Product Specifications Electrical Specifications Mechanical SpecificationsInput OutputSwitches and Displays Important Safety Instructions Para Systems Life Support PolicyHazardous Voltage Installation and Operation InstallationCommunication Port RS-232 IinterfaceWiring Description Rear ViewOutput Voltage Configurations Output Configuration #5 = 240VAC Troubleshooting Troubleshooting ChartObtaining Service Minuteman UPS Application Notes START-UP1 Inverter Mode 1 Bypass Mode Bypass Short Alarm Limited Product Warranty Declaration of Conformity Page 34000139 Rev