Minuteman UPS MCP 10001, MCP 6001 Product Specifications Electrical Specifications, Input, Output

Page 4

1.3PRODUCT SPECIFICATIONS ELECTRICAL SPECIFICATIONS

Model

Power

Freq.

Input

Output

No.

Rating

(Hz)

 

 

 

 

 

 

Voltage

Current

Voltage

Current

 

 

 

 

MCP 6001

6KVA

50/60

 

170-276

33A

120, 120/120, 208,

50, 25/25, 28.8,

 

4.2KW

 

 

VAC

 

120/208, 240, 120/240V

25/28.8, 25, 25/25A

MCP10001

10KVA

50/60

 

170-276

56A

120, 120/120, 208,

83.3, 41.7/41.7, 48.1,

 

7KW

 

 

VAC

 

120/208, 240, 120/240V

41.7/48.1, 41.7, 41.7/41.7A

INPUT

Voltage:

As listed

Phase:

single phase with ground

Frequency:

50/60Hz +/- 5%, auto selection

Power factor:

>/= 0.97

OUTPUT

Output voltage regulation:

+/-3%

Power factor:

0.7 lag to unity

Frequency regulation:

+/-5%, phase lock to input under normal conditions, +/-0.5% of nominal frequency,

 

under normal operation or battery mode.

Distortion:

+/-3.0% THD at full linear load, +/-7% THD at full non-linear load

Overload Capacity:

>130% +/-10% for 200 ms, 105% for 10 second

Load Crest Ratio

3:1 maximum

OPERATING ENVIRONMENT

Ambient temperature:

10 to 40 degrees Centigrade

Operation humidity:

20% to 90%, non-condensing

Altitude:

less than 1500M above sea level

Storage temperature:

-15 to 40º C

MECHANICAL SPECIFICATIONS

Model Number

Dimensions

Weight

 

H x W x D

Net (Shipping)

MCP 6001

31.5 x 10.25 x 23.25 in.

296(311.6)lb.

 

80 x 26 x 59 cm

134.3(141.3)Kg

 

 

 

MCP10001

38 x 13.5 x 26.5 in.

519.6(552.2)lb.

 

96.5 x 34.3 x 67.3 cm

235.7(250.5)Kg

 

 

 

Page 2

Image 4
Contents Continuous Power Series User’s Manual MCP Table of Contents Introduction Explanation of SymbolsSystem Description Product Specifications Electrical Specifications Mechanical SpecificationsInput OutputSwitches and Displays Important Safety Instructions Para Systems Life Support PolicyHazardous Voltage Installation and Operation InstallationCommunication Port RS-232 IinterfaceWiring Description Rear ViewOutput Voltage Configurations Output Configuration #5 = 240VAC Troubleshooting Troubleshooting ChartObtaining Service Minuteman UPSApplication Notes START-UP1 Inverter Mode 1 Bypass Mode Bypass Short Alarm Limited Product Warranty Declaration of Conformity Page 34000139 Rev