Minuteman UPS SNMP-NV6 user manual 1.2 TCP/IP Setting

Page 12

SNMP-NV6

4.4.1.2 TCP/IP Setting

+========================+ TCP/IP Setting +========================+

[1].IPv4 Address: 192.168.001.100

[2].IPv4 Subnet Mask: 255.255.255.000

[3].IPv4 Gateway IP: 192.168.001.254

[4].IPv4 DNS or WINS IP: 192.168.001.001

[5].DHCPv4 Client: Enable

[6].IPv6 Address: fe80::230:abff:fe25:900

[7].IPv6 Prefix Length: 64

[8].IPv6 Gateway IP: ::

[9].IPv6 DNS IP: ::

[a].DHCPv6: Enable

[b].Host Name (NetBIOS): SNMP-NV6

[c].System Contactor:

[d].System Location:

[e].Auto-Negotiation: Enable

[f].Speed: 100M

[g].Duplex: Full

[h].Status Stable: 3

[0].Back To Previous Menu Please Enter Your Choice =>

Item

Function

Description

Default

[1].

IPv4 Address

The default IPv4 address

192.168.001.100

[2].

IPv4 Subnet Mask

The IPv4 sub-net mask setting

255.255.255.000

[3].

IPv4 Gateway IP

The IPv4 network default gateway

192.168.001.254

[4].

IPv4 DNS IP

IPv4 Domain Name Server IP address

192.168.001.001

[5].

DHCPv4 Client

Enable/Disable DHCPv4 protocol

Enable

[6].

IPv6 Address

The SNMP-NV6 IPv6 address

 

[7].

IPv6 Subnet Mask

The IPv6 sub-net mask setting

 

[8].

IPv6 Gateway IP

The IPv6 network default gateway

 

[9].

IPv6 DNS IP

IPv6 Domain Name Server IP address

 

[a].

DHCPv6 Client

Enable/Disable DHCPv6 protocol

Enable

[b].

Host Name

 

SNMP-NV6

[c].

System Contactor

 

 

[d].

System Location

 

 

[e].

Auto-Negotiation

 

Enable

[f].

Speed

The network link operation

100M

[g].

Duplex

 

Full

Page 12

Image 12
Contents SNMP-NV6 Safety Information About this manualSave this Manual Electromagnetic InterferenceTable of Contents Upgrade Specifications Features OverviewPackage Contents DescriptionPorts Installation LED IndicatorsDipswitch Settings Configuration Methods Configure the SNMP-NV6 card by EzSettingConfigure the SNMP-NV6 card through COM Port Configure the SNMP-NV6 card through Telnet Configure the SNMP-NV6 card via Text ModeSNMP-NV6 card’s Main Menu User Manager Radius1.2 TCP/IP Setting Network Parameter Reset All To Default Time ServerSoft Restart Exit Without SaveWeb Interface Run a Web BrowserUPS Information Battery Parameters UPS Properties3 In/Out Parameters IdentificationConfigure Status IndicationUPS Management Low Battery Battery Replacement DateExternal Battery Pack Auto RestartBattery Test ControlShutdown & Restart UPS Only Power Fail/Restore Simulation Outlet ControlWeekly Schedule Administration User Manager Specific Schedule2 TCP/IP 2.1 IPv42.2 IPv6 System3 Web 3.1 WebSSL Certificate Console Host Key5 FTP 5.1 FTPTime Server Batch Configuration Simple Network Time ServerManual SyslogUpgrade Snmp Access Notification Event LevelSNMPv3 USM User Based Management Snmp Trap Mail Server Wake On LAN History Event LogHistory Configure Data LogEnvironment Information Configuration Upgrade SNMP-NV6 Specifications Technical SpecificationsDIP Switch Settings LED IndicatorsTroubleshooting Web Browser, I can see the Login page but cannot loginAm unable to perform the Snmp Get operation? For Windows Version Limited Product Warranty