Maintenance

If the Coll LED is flashing, the module is reporting collisions on the Ethernet network. While such collisions are normal, the frequency of the flashes is an indication of the volume of traffic on the network. The flashes may be so frequent that the LED appears to be shining steadily. Heavy traffic will slow communications. If response time is important to your application, you should consider segmenting your network to reduce the frequency of collisions.

6.1.8Application LED

If the module crashes, it will note the reason in a log. If the module is able to recover, the Appl LED will light, indicating that an entry has been made in the error log. To learn how to read and clear the error log, refer to the section below.

6.1.9Reading and Clearing the Error Log

If the Appl indicator is lit, entries have been made in the error log. The log may hold up to 1023 entries. If the error log is full, the Fault indicator will remain on and the module will be unable to recover until the log is cleared.

You may read the error log while the controller is running or stopped, using the ER- RLOG utility. However, if you plan to clear the error log, you must stop the controller first. During the program, ERRLOG will ask you whether you want to stop the con- troller. If you respond yes, it will stop and restart the controller for you.

CAUTION

PROCESS INTERRUPTION

Do not stop the controller unless it is safe to stop the operations it is controlling. When a controller is stopped, all operations under its control will also stop.

Failure to observe this precaution can result in injury or equipment damage.

To read the error log, at the DOS prompt in the appropriate directory, type:

ERRLOG <routing path> <slot> [/d] [/sxx] [/ny]

where <routing path> is the Modbus Plus address of the Quantum PLC <slot> is the slot number of the Ethernet web embedded server module. [/d] is optional, to enable debug messages. Default is no debug.

[/sxx] is optional and specifies the software interrupt to use, xx in hexadecimal. The default is 5c.

[/ny] is optional and specifies the Modbus Plus adapter number to use, y.

840 USE 115 00 Version 1.0

57

Image 67
Contents USE 115 00 Version Modicon Quantum EthernetTraining USE 115 00 Vesion Modicon Quantum EthernetOctober Document Set Preface USE 115 00 Version Contents Retrieving Data via the World Wide Web Using the Network Options Ethernet TesterChapter Maintenance Mstr InstructionAppendix D Suppliers Glossary Index Appendix a SpecificationsContents Viii About This Book Document Scope Related Documentation Validity NoteBenefits of Quantum Design Introduction Ethernet Web Embedded Server ModulesType of Cable Network Part Number Models for Fiber Optic and Twisted Pair Cable SystemsRemovable Door Front Panel Components140 NOE 251 LED Display Color Indication When OnInternet Protocol IP Network Address Label Address LabelsEthernet Address Label0 B 7 2 a Example Calculating the Derived IP Network AddressLocate the global address label on Front panel of the moduleFiber Optic Connectors Twisted Pair ConnectorTransmit Data Network Options Ethernet Tester Utility DisketteErrlog Meeting the Demands of Your Application Ethernet and Your ApplicationGuidelines for Designing Your Network CompatibilityTraffic DelaysUsing Switches SegregatingVerifying the Default Configuration Installing and Configuring Module Before You BeginImproper Network Topologies Verifying that the Network Has Been Constructed ProperlyAre You Really Ready to Install? Check Installing the ModuleMounting the Module on the Backplane Snap into place Connecting the CableWith connectors 990 XCA 656 Twisted PairAttaching the Cable Configuring the Module with Modsoft Changing the Default ConfigurationAssigning a Slot Number Selecting the Ethernet Framing TypeResetting the Module Assigning the Default Gateway Address and Subnet MaskAssigning the IP Network Address Configuring More Than One Ethernet Module Parameter Dialog for an Ethernet Web Embedded Server Module Configuring the Module with ConceptMstr Description Mstr Instruction IntroductionMstr Operation Code TCP/IP Ethernet Support Opcode BF hex CharacteristicsSize CompatibilityOutputs ContentRepresentation InputsBottom Node Mstr Function Error CodesError Codes Middle NodeSs Hex value Meaning Hex Error Code MeaningHex Error Code Meaning 5016 An argument is valid Information as described in the following table Read and Write Mstr OperationsControl Block UtilizationStatistics information as described in the following table Get Local Statistics Mstr OperationGet Remote Statistics Mstr Operation Clear Local Statistics Mstr OperationClear Remote Statistics Mstr Operation Health Status Peer Cop Health Mstr OperationPeer Cop CommunicationsStatus Index Type WordRead CTE Config Extension Table Mstr Operation Reset Option Module Mstr OperationModule information as described in the following table Registers. The registers display the following CTE data Parameter Register ContentCTE Display ImplementationWrite CTE Config Extension Table Mstr Operation Word Meaning 13 TCP/IP Ethernet StatisticsRetrieving Data via the World Wide Web Introduction Web Utility Home Accessing the Web Utility HomeQuantum Web Utility Web Utility for QuantumRetrieving Data via the World Wide Web Using the Network Options Ethernet Tester Introduction Establishing a Connection with an Ethernet Module Installing the Network Options Ethernet TesterMain Menu Get Statistics Box Getting and Clearing StatisticsSample Statistics MAC AddressUsing the Network Options Ethernet Tester Read Register Box Reading and Writing RegistersWrite Register Box Detecting Errors Maintenance Responding to ErrorsReady LED Active LEDLink LED Fault LEDKernel LED LED Display for Improperly Connected Twisted Pair Cable Collision LEDApplication LED Reading and Clearing the Error LogEBX, EBP, ESI, EDI, ESP, EFLAGS, EIP Default is Example Errlog 49To restart the controller, type Y Example Sample Error LogHot Swapping An Ethernet Module From the Device to Download menu, select Local Head Downloading a New Software ImageUSE 115 00 Version Storage Conditions SpecificationsPower Dissipation Bus Current Required Operating Conditions Communication PortsSpecifications References Ethernet Developers Guide IntroductionDevelopment Environment OverviewClass Descriptions CSampledoc Class CSampleView Class Accessing TCP/IPEvent Description Network Event Member Function Application Message FormatTransaction Processing TimersTransmit State Machine Exists the loop Receive State Machine Ethernet Developers Guide Displaying on the Screen Quantum Ethernet TCP/IP Modbus Application Protocol Counts and data offsets Modbus Application Protocol PDUIncludes the dstid and data fields Is defined belowModbus Application Protocol Service Classes Modbus Application Protocol PDU Analysis Quantum Ethernet TCP/IP Modbus Application Protocol Broadcast/Multicast TCP/IP Specific IssuesTCP Port Number Reference Documents Quantum Ethernet TCP/IP Modbus Application Protocol Suppliers Suppliers Bridge GlossaryAddress BpsFraming types Default gatewayField FrameIO Map HubInternet IP AddressProtocol OSI modelPacket PortSubnet SwitchSocket StackGlossary Index Index Network Options Ethernet Tester World Wide Web server Mstr