INSTALLATION MANUAL | 5 |
1. Control Panel Design Guidelines
Pay careful attention to the placement of system components and associated cable routing. These items can significantly enhance the performance and integrity of your control application.
GROUND
STRAP
OIT REAR
COVER
OIT
QUIET
GROUND
SHIELDED
COMMUNICATION
CABLE
| CONTROLLER | CONTROL PANEL |
OIT OPERATING | TIED TO RELIABLE | |
CABLE |
| EARTH GROUND |
OIT |
|
|
POWER |
|
|
SUPPLY |
|
|
LINE | I / O CONTROL LINES | POWER LINE |
FILTER |
| |
| GROUND WIRES | FILTER |
|
| |
| QUIET GROUND(ISOLATED) |
|
Figure 1 Control Panel Example
1.1.Control Panel Grounding
•The control panel should be connected to a good,
•Hinged doors on control panels do not provide a long term electrical connection to the rest of the enclosure. Corrosion develops over time and prevents good electrical contact. For this reason, a separate wire braid should be installed from the hinged control panel to the rest of the enclosure.
1.2.Power Supply Selection
•The power supply used to power the OIT should have an output between +12 and +30 VDC. The voltage should measure between +12 and +30V at the OIT between Pins 2 and 3 of the OIT terminal block. A 24 VDC, 0.5 amp linear power supply dedicated to the OIT is recommended.
•The power leads on the operating cable for the OIT should be 18AWG