B&B Electronics MAP450D installation manual RS-422/485 Network mode, Oit

Page 10

10

MAP450D

2.3. RS-422/485 (Network mode)

Network mode supports the 3-wire and 5-wire RS-422/485 configurations. The 3-wire configuration has both transmit and receive on the same pair of wires plus a signal common. The 5-wire configuration has differential signal pairs for transmit and receive plus a signal common. In both configurations the signal pairs must be twisted and surrounded by an overall shield.

OIT

 

TB1

 

 

1

Shield

 

 

+24V

2

 

* COM

3

 

RXD+

4

 

RXD-

5

 

TXD+

6

 

TXD-

7

 

* RTN

8

 

*RTN and COM are internally connected in OIT.

Power Supply

+24V

GND

From or To

Host or OIT

CHASSIS GND

RXD+/TXD+

RXD-/TXD-

SIG GND

SIG GND

Figure 5 3-Wire RS-422/485 (Network mode)

NOTE: When using 3-wire RS-422/485, Jumper JP4 must be in position “B”. Refer to section 2.4 for instructions.

OIT

 

TB1

 

 

1

Shield

 

 

+24V

2

 

* COM

3

 

RXD+

4

 

RXD-

5

 

TXD+

6

 

TXD-

7

 

* RTN

8

 

*RTN and COM are internally connected in OIT.

Power Supply

+24V

GND

From or To

Host or OIT

CHASSIS GND

TXD+

TXD-

RXD+

RXD-

SIG GND

SIG GND

Figure 6 5-Wire RS-422/485 (Network mode)

5-wire RS-422/485 supports full-duplex communications; which means that the host controller can trasmit data to the OITs and receive data from the OITs at the same time. 3-wire RS-422/485 only supports half-duplex communications; which means that the host controller cannot transmit and receive data at the same time. Although 3-wire RS-422/485 installations may be less costly than 5-wire installations, the increased complexity in programming the host controller for 3-wire RS-422/485 may increase development time.

1010-0046A, REV 00

Image 10
Contents Installation Manual Applications Assistance Static Awareness Read Me FirstIntroduction Unpacking the UnitTable of Contents Control Panel Design Guidelines Power Supply SelectionControl Panel Grounding OIT Cable Routing Other Steps to Improve Noise ImmunityConnecting the MAP450D to a Host Controller Host/ControllerFerrite coil RS-232 Interactive & Block modes RS-422/485 Interactive & Block modesRS-422/485 Network mode OITOIT #2 Network Termination Set Jumper for 3-Wire RS-422/485 Cable shield must not be used as the signal groundMounting the MAP450D Panel MountPedestal/Pendent Mount MAP450D Pedestal MountingBenchtop Mount Mounting PlateConfiguring the MAP450D Connecting the MAP450D to a PCAppendix a OIT Hardware Specifications MechanicalAppendix a con’t Dimensional Outline Front View Rear ViewAppendix B Differences Between MAP450D and MAP450B