B&B Electronics MAP450D installation manual Set Jumper for 3-Wire RS-422/485

Page 13

INSTALLATION MANUAL

13

The cable shield must not be used as the signal ground.

It is tempting to try and reduce the cost of 5-wire cabling by using a 4-wire cable with the shield used as the signal ground. DON’T DO IT. The initial cost savings are always exceeded by the maintenance costs once the system is operating under field conditions. It is often necessary to completely replace the network com-link with the proper cable (5-wire plus shield) to eliminate noise problems in the system.

The signal ground must not be connected to the chassis or earth ground. The chassis or earth ground is intended as a safety ground for power supplies, EMI filters, voltage spike protection circuits, 120 VAC neutral returns, and all manner of AC and DC driven devices. As a result, the chassis or earth ground can carry large voltage potentials and currents. Connecting the signal ground to chassis or earth ground can damage the devices connected to the com-link.

2.4. Set Jumper for 3-Wire RS-422/485

This step is required only if the OIT will be communicating with the host controller using RS-485 half-duplex 3-wire communication.

JP4A

(Display)

B

(CPU Board)

JP4

A

B

 

A

 

JP4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Position "A",

Position "B",

Normal

Half-Duplex 3-Wire

 

 

 

RS485

Figure 7 MAP450D Jumper Installation

STEPS

1.Remove the protective cover from the rear of the unit.

CAUTION: When the rear cover is removed, the circuitry inside is exposed to possible damage by electrostatic discharge. Refer to Static Awareness on page 4.

2.Locate jumper “JP4” using Figure 7 as a guide. The jumper is installed on the upper two pins of a 3-pin header. This is called Position “A”.

3.Move the jumper to the lower two pins of the 3-pin header (Position “B”). Ensure that the jumper is pressed fully into place.

4.Replace the rear cover and the four retaining screws.

1010-0046A, REV 00

Image 13 Contents
Installation Manual Applications Assistance Introduction Read Me FirstStatic Awareness Unpacking the UnitTable of Contents Control Panel Design Guidelines Power Supply SelectionControl Panel Grounding Other Steps to Improve Noise Immunity OIT Cable RoutingHost/Controller Connecting the MAP450D to a Host ControllerFerrite coil RS-422/485 Interactive & Block modes RS-232 Interactive & Block modes OIT RS-422/485 Network modeOIT #2 Network Termination Cable shield must not be used as the signal ground Set Jumper for 3-Wire RS-422/485Panel Mount Mounting the MAP450DMAP450D Pedestal Mounting Pedestal/Pendent MountMounting Plate Benchtop MountConnecting the MAP450D to a PC Configuring the MAP450DMechanical Appendix a OIT Hardware SpecificationsFront View Rear View Appendix a con’t Dimensional OutlineAppendix B Differences Between MAP450D and MAP450B