2. Installation
HotSwap MBP-module operation
UPS ON - OK to switch | Normal | BY PASS SWITCH |
51 | 52 | 53 |
The HotSwap MBP module has a rotary switch (53) with two positions:
Normal - the load is supplied by the UPS, Bypass - the load is supplied directly by the
UPS start-up with the HotSwap MBP module
1 - Check that the UPS is correctly connected to the HotSwap MBP module.
2 - Set switch (53) to the Normal position.
3 - Start the UPS by pressing the ON/OFF button (27) on the UPS control panel. The load is supplied by the UPS.
LED (51) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP-module test
1 - Set switch (53) to the Bypass position and check that the load is still supplied. 2 - Set switch (53) back to the Normal position.
2.7 UPS connection without a FlexPDU or HotSwap MBP module
Check that the indications on the name plate located on the back of the UPS correspond to the
|
| 1 - Connect the supplied cable (31) (250 V - |
|
| 16 A) to the socket (10), then to the |
|
| source. |
|
| 2 - Connect the loads to the UPS using the |
|
| cables (32). |
|
| It is preferable to connect the priority loads to |
|
| the four outlets marked (9) and the non- |
7 |
| priority loads to the four outlets marked (8) |
| that can be programmed in pairs (1 and 2). | |
|
| |
|
| Connect any |
8 |
| outlet (7). |
|
| |
9 |
| To program shutdown of outlets (8) during |
|
| operation on battery power and thus optimise |
|
| the available backup time, the MGE UPS |
35 |
| SYSTEMS communications software is |
|
| required. |
|
| 3 - Fit the connection securing system (35) |
|
| that prevents the plugs from being pulled out |
10 | 32 | accidentally. |
|
|
31
Note. The UPS charges the battery as soon as it is connected to the
Once the UPS is connected to the