4. Access to measurements and personalisation data
Output personalisation
Function | Factory setting | Other available settings | Comments |
|
|
|
|
Output voltage (1) | 230 Volts AC | 200/208/220/240 Volts AC |
|
|
|
|
|
Frequency converter (1) | Disabled | Enabled | The connected devices are never |
|
|
| transferred to the bypass. |
|
|
|
|
Output frequency (1) | Automatic selection | 50 or 60 Hz | User selectable only if the |
|
|
| |
|
|
| enabled. |
|
|
|
|
Transfer to the bypass AC | Bypass AC power must | Bypass AC power may be |
|
input (1) | be within tolerances | outside tolerances |
|
|
|
|
|
Overload level (1) | 102% | 50 / 70% | Alarm if threshold is overrun. |
|
|
|
|
(1)These parameters may be modified only when the UPS is OFF. Detailed comments are available in the Personal
ON/OFF personalisation
Function | Factory setting | Other available settings | Comments |
|
|
|
|
Start on battery power | Enabled | Disabled |
|
|
|
|
|
Automatic restart | Enabled | Disabled | The UPS restarts automatically when |
|
|
| AC power returns. |
|
|
|
|
Energy savings | Disabled | Enabled | When function enabled, battery shuts |
|
|
| down when power drops to <5%. |
|
|
|
|
Detection of phase/ | Disabled | Enabled | When function enabled, the UPS |
neutral inversion (SWF) |
|
| remains OFF if the system detects |
|
|
| phase/neutral inversion. |
|
|
|
|
Battery personalisation
Function | Factory setting | Other available settings | Comments |
|
|
|
|
Battery test | Weekly test | No test / daily test / |
|
|
| monthly test |
|
|
|
|
|
20% | 0 to 100% | Adjustable in 1% steps. | |
|
|
|
|
Selection of the backup | Automatic detection of | 65 to 400 Ah |
|
time | number of battery |
|
|
| modules |
|
|
|
|
|
|
Battery protection against | Enabled | Disabled | When function disabled, MGE UPS |
excessive discharges |
|
| SYSTEMS warranty no longer |
|
|
| applies. |
|
|
|
|
4.4Personalisation using external software
◗Insert the
◗On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal
◗Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of the Personal