MGE UPS Systems 3000 RT 2U Personalisation using external software, Output personalisation

Page 17

4. Access to measurements and personalisation data

Output personalisation

Function

Factory setting

Other available settings

Comments

 

 

 

 

Output voltage (1)

230 Volts AC

200/208/220/240 Volts AC

 

 

 

 

 

Frequency converter (1)

Disabled

Enabled

The connected devices are never

 

 

 

transferred to the bypass.

 

 

 

 

Output frequency (1)

Automatic selection

50 or 60 Hz

User selectable only if the

 

 

 

frequency-converter function is

 

 

 

enabled.

 

 

 

 

Transfer to the bypass AC

Bypass AC power must

Bypass AC power may be

 

input (1)

be within tolerances

outside tolerances

 

 

 

 

 

Overload level (1)

102%

50 / 70%

Alarm if threshold is overrun.

 

 

 

 

(1)These parameters may be modified only when the UPS is OFF. Detailed comments are available in the Personal Solution-Pacsoftware.

ON/OFF personalisation

Function

Factory setting

Other available settings

Comments

 

 

 

 

Start on battery power

Enabled

Disabled

 

 

 

 

 

Automatic restart

Enabled

Disabled

The UPS restarts automatically when

 

 

 

AC power returns.

 

 

 

 

Energy savings

Disabled

Enabled

When function enabled, battery shuts

 

 

 

down when power drops to <5%.

 

 

 

 

Detection of phase/

Disabled

Enabled

When function enabled, the UPS

neutral inversion (SWF)

 

 

remains OFF if the system detects

 

 

 

phase/neutral inversion.

 

 

 

 

Battery personalisation

Function

Factory setting

Other available settings

Comments

 

 

 

 

Battery test

Weekly test

No test / daily test /

 

 

 

monthly test

 

 

 

 

 

Low-battery warning

20%

0 to 100%

Adjustable in 1% steps.

 

 

 

 

Selection of the backup

Automatic detection of

65 to 400 Ah

 

time

number of battery

 

 

 

modules

 

 

 

 

 

 

Battery protection against

Enabled

Disabled

When function disabled, MGE UPS

excessive discharges

 

 

SYSTEMS warranty no longer

 

 

 

applies.

 

 

 

 

4.4Personalisation using external software

Insert the Solution-PacCD-ROM in the drive.

On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal Solution-Pacsoftware.

Then select "Settings", "Advanced settings" and "UPS settings".

Note that the Linux/Unix/MacOS versions of the Personal Solution-Pacsoftware do not offer this possibility.

34007776EN/AB - Page 17

Image 17
Contents Pulsar M 34007776EN/AB Environmental protection IntroductionSubstances PackingPictograms Contents Weights in kg Dimensions H x W x D in mmPresentation Standard positionsRear panels Pulsar M EXB optional battery moduleControl panel Pulsar M 2200Unpacking and contents check InstallationInstallation in tower position Installation in rack position Connection of RS232 or USB communication port optional Installation of the communication cards optionalCommunication ports FlexPDU module Connections with a HotSwap MBP module optionalHotSwap MBP-module operation UPS connection without a FlexPDU or HotSwap MBP moduleUPS start-up with the HotSwap MBP module HotSwap MBP-module testStart-up and normal operation Operation on battery powerOperation Using the UPS remote control functions Return of AC powerEnd of battery backup time Remote control connection and testROO RPO Access to measurements Access to measurements and personalisation dataPersonalisation using the control panel Display menus arrangementBattery personalisation Personalisation using external softwareOutput personalisation ON/OFF personalisationIndication Diagnostic Correction MaintenanceTroubleshooting Troubleshooting a UPS equipped with the HotSwap MBP module Battery-module replacementSafety recommendations Battery-module removalMounting the new battery module Maintenance on a UPS equipped with the HotSwap MBP moduleMaintenance Return to normal operationHz training centre Training centreMGE UPS Systems FranceAppendices Technical specificationsGlossary 34007776EN/AB