5. Maintenance
Troubleshooting a UPS equipped with the HotSwap MBP module
| Indication | Diagnostic | Correction | ||
|
|
|
|
| |
10 | The load is no longer supplied when | ◗ | The protected devices are | Check the wiring between the UPS | |
| the rotary switch (49) on the HotSwap | connected to the UPS output | and the HotSwap MBP module (see | ||
| MBP module is set to the Bypass | instead of to the HotSwap MBP | section 2.6). | ||
| position. | module. |
|
| |
|
| ◗ | The |
|
|
|
| to the UPS input instead of to the |
|
| |
|
| HotSwap MBP module. |
|
| |
|
|
|
|
|
|
11 | The load is no longer supplied when | ◗ | The UPS is shut down. | ◗ | Start the UPS. |
| the rotary switch (49) on the HotSwap | ◗ | The wiring between the UPS and | ◗ | Check the wiring between the UPS |
| MBP module is set to the Normal | the HotSwap MBP module is not | and the HotSwap MBP module (see | ||
| position. | correct. | section 2.6). | ||
|
|
|
|
|
|
12 | The load is no longer supplied if AC- | ◗ | The rotary switch (49) on the | ◗ | Set the rotary switch (49) on the |
| power fails. | HotSwap MBP module is set to the | HotSwap MBP module to the | ||
|
| Bypass position. | Normal position. | ||
|
| ◗ | The wiring between the UPS and | ◗ | Check the wiring between the UPS |
|
| the HotSwap MBP module is not | and the HotSwap MBP module (see | ||
|
| correct. | section 2.6). | ||
|
|
|
|
|
|
If a fault leads to UPS shutdown, press the ON/OFF button (27) to clear the fault.
5.2 Battery-module replacement
Safety recommendations
The battery can cause electrocution and high
◗Remove watches, rings, bracelets and all other metal objects from the hands and arms,
◗Use tools with an insulated handle.
Battery-module removal
A - Unscrew the
B - Remove the part.
B
A
C - Disconnect the battery block by separating the two connectors (never pull on the wires).
C