MGE UPS Systems Comet TM 5 - 30 kVA user manual Connection of power cables figures 10 to

Page 13

connection of power cables (figures 10 to 14)

Make sure the unit is powered down and disconnected from all input power before making connections to the terminal blocks at the front or back of the cubicle (depending on the type of Comet).

For protection of life and property, earth wires should always be connected first.

For Comet 31 series or Comet 33 series devices, the Mains power supply must be with a neutral cable.

For Comet 33 series, the neutral may be reconstituted by a complete insulation transformer option (a transformer with a triple-point structure).

Neutral system: identical upstream and downstream neutral systems (no galvanic isolation). Comet can be used with all types of neutral systems, on the condition that standard practices be respected.

check that AC input power circuit breaker, installed upstream on the low voltage switchboard, is in off (O) position;

check that the input power switch 1 and the battery circuit breaker 4 are in off (O) position.

Connection sequence for 5 kVA Comet:

open the protective cover 44 (secured by 2 screws) and the connection cover panel 13 (secured by 6 screws);

strip the duct of the AC input power and load cables over a length of 7 cm;

strip each wire over a length of 1 cm;

insert the cables of the AC input power and load through the bushings of the connection cover panel;

connect the cables of the AC input power to "Mains 1" XR1 terminal block in the order shown on the label;

connect the load cables to the "load" XR2 terminal block in the order shown on the label;

connect the various options as shown in the relevant section for each one in this manual;

when the cables have been connected, the duct of each cable must be tightened by a binding band against the horizontal binding bar placed beneath the terminal block in order to protect the conductors from tensile loads;

put back the connection cover panel 13 and the protective cover 44 .

Merlin Gerin by MGE UPS SYSTEMS

Comet installation and user manual: E-6761200XT/FC

2.3

Image 13
Contents Comet 30 kVA Merlin GerinSafety recommendations Sikkerhedsforskrifter NorskRecomendações de segurança PortuguêsTurvallisuusohjeet SuomalainenSäkerhetsföreskrifter SvenskContents Options Maintenance and servicingAppendices GlossaryConfiguration Safety information Identification to CometIntroduction to Comet Identification plateKey for figures 2 to Functional diagramFinal positioning figure GeneralComet layout seen from above Special precautions InstallationElectrical diagram for power connections Connection diagram for a single AC inputConnection sequence for 5 kVA Comet Connection of power cables figures 10 toConnections for Comet series 31 5kVA Connections for Comet series 11 5kVAConnections for Comet series 11 7.5/10kVA Connection sequence for Comet other than 5kVAConnections for Comet series 33 10/15/20/30kVA Connections for Comet series 31 7.5/10/15/20kVABasic controls and indications Controls and indicationsControls and indications Key to figureThis light indicates that Comet is Inverter on button Inverter off button BuzzerBuzzer reset Controls and diagnostics display figureFault reset Diagnostics displayManual maintenance bypass switch Powering up to CometStart-up Preliminary checksInverter start-upsystem in manual start-up mode Shutdown Powering downInverter shutdown Merlin Gerin by MGE UPS Systems Operation Operation on battery power figureNormal operation Return of AC input power Battery durationInverter Overload curve Battery monitoring testsOverloads on 5 kVA Comet S11 or S31 When an overload occursStatic bypass Overload curve Mains 2 out of tolerance Merlin Gerin by MGE UPS Systems Alarm indications table AlarmsStatus or action producing the indication End of battery power Battery circuit breaker in off positionManual bypass Chopper overtemperature see faultManual bypass switch SUB-D 15-pin connector SUB-D 15-pin connector connectionCommunication Standard functionsContact Monitor PlusTalk Jbus / RS232 and Jbus / RS485Safety reminder Preventive maintenance by user Maintenance and servicingBattery maintenance Visual checkCustomer training Maintenance contractsAnnual check Additional battery cell characterisitics Extended battery cabinetOptions Connection of an additional battery cabinet Connection of an additional battery cabinetEmergency off Connection diagram for MX shunt trip to terminal block XR3Shunt trip connection Full galvanic isolation transformer standard Comet equipment Power connection diagramsSeparate Mains 2 transformer AC bypass input Power connection diagramFrequency converter Hot standby system Harmonics filter Full isolation transformer and separate Mains 2 transformer Combined optionsFull isolation transformer and harmonics filter Example of a Comet seriesRelative positions of the various cubicles Separate Mains 2 transformer and harmonics filterRange characteristics General characteristicsAppendices Comet series 11 general characteristics Comet series 31 general characteristics Comet series 33 general characteristics Selection of cable cross-sections Selection of protection devices Schematic diagram for protection devices11.7 Connection of the cable shielding Glossary 12.2 6761200XT MGE UPS Systems S.A

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.