MGE UPS Systems Comet TM 5 - 30 kVA user manual Selection of protection devices

Page 54

appendices (cont')

selection of protection devices

Selection of protection devices installed upstream (CB1) or downstream (CB2) from Comet depends on:

the rated line current;

the required breaking capacity.

Schematic diagram for protection devices

CB2

LV switchboard

CB1

Comet

CB2

To ensure discrimination during overloads or short-circuits, the following protection devices are recommended:

Comet

Comet rated

Merlin Gerin

Merlin Gerin

 

output (kVA)

circuit breaker CB1

circuit breaker CB2

series 11

5

C60N 32A (curve D)

C60L 6A (curve Z)

 

 

 

 

 

7.5

C60N 40A (curve D)

C60N 10A (curve B)

 

 

 

 

 

10

C60N 63A (curve D)

C60N 10A (curve B)

series 31

5

C60N 25A (curve D)

C60L 6A (curve Z)

 

 

 

 

 

7.5

C60N 40A (curve D)

C60N 10A (curve B)

 

 

 

 

 

10

C60N 50A (curve D)

C60N 10A (curve B)

 

 

 

 

 

15

NC100H 80A (curve D)

C60N 25A (curve B)

 

20

NC100H 100A (curve D)

C60N 25A (curve B)

series 33

10

C60N 40A (curve D)

C60L 6A (curve Z)

 

 

 

or C60N 6A (curve B)

 

 

 

 

 

15

C60N 40A (curve D)

C60L 6A (curve Z)

 

 

 

or C60N 5A (curve B)

 

20

C60N 63A (curve D)

C60L 16A (curve Z)

 

 

 

or C60N 10A (curve B)

 

 

 

 

 

30

NC100H 80A (curve D)

C60L 16A (curve Z)

 

 

 

or C60N 10A (curve B)

Note:

The breaking capacity of the protection devices must be greater than the prospective short-circuit current.

Consult the Merlin Gerin Low Voltage Application Guide for further details.

Selection of the trip units for the circuit breakers installed upstream of the transformers must take the inrush currents (10 to 14In) into account.

11.6

Comet installation and user manual: E-6761200XT/FB

Merlin Gerin by MGE UPS SYSTEMS

Image 54
Contents Merlin Gerin Comet 30 kVASafety recommendations Norsk SikkerhedsforskrifterPortuguês Recomendações de segurançaSuomalainen TurvallisuusohjeetSvensk SäkerhetsföreskrifterContents Appendices Maintenance and servicingOptions GlossaryIntroduction to Comet Safety information Identification to CometConfiguration Identification plateFunctional diagram Key for figures 2 toGeneral Final positioning figureComet layout seen from above Electrical diagram for power connections InstallationSpecial precautions Connection diagram for a single AC inputConnection of power cables figures 10 to Connection sequence for 5 kVA CometConnections for Comet series 11 5kVA Connections for Comet series 31 5kVAConnection sequence for Comet other than 5kVA Connections for Comet series 11 7.5/10kVAConnections for Comet series 31 7.5/10/15/20kVA Connections for Comet series 33 10/15/20/30kVAControls and indications Controls and indicationsBasic controls and indications Key to figureThis light indicates that Comet is Buzzer Inverter on button Inverter off buttonFault reset Controls and diagnostics display figureBuzzer reset Diagnostics displayStart-up Powering up to CometManual maintenance bypass switch Preliminary checksInverter start-upsystem in manual start-up mode Powering down ShutdownInverter shutdown Merlin Gerin by MGE UPS Systems Operation on battery power figure OperationNormal operation Battery duration Return of AC input powerBattery monitoring tests Inverter Overload curveWhen an overload occurs Overloads on 5 kVA Comet S11 or S31Static bypass Overload curve Mains 2 out of tolerance Merlin Gerin by MGE UPS Systems Alarms Alarm indications tableStatus or action producing the indication Battery circuit breaker in off position End of battery powerChopper overtemperature see fault Manual bypassManual bypass switch Communication SUB-D 15-pin connector connectionSUB-D 15-pin connector Standard functionsTalk Monitor PlusContact Jbus / RS232 and Jbus / RS485Battery maintenance Maintenance and servicingSafety reminder Preventive maintenance by user Visual checkMaintenance contracts Customer trainingAnnual check Extended battery cabinet Additional battery cell characterisiticsOptions Connection of an additional battery cabinet Connection of an additional battery cabinetConnection diagram for MX shunt trip to terminal block XR3 Emergency offShunt trip connection Power connection diagrams Full galvanic isolation transformer standard Comet equipmentPower connection diagram Separate Mains 2 transformer AC bypass inputFrequency converter Hot standby system Harmonics filter Full isolation transformer and harmonics filter Combined optionsFull isolation transformer and separate Mains 2 transformer Example of a Comet seriesSeparate Mains 2 transformer and harmonics filter Relative positions of the various cubiclesGeneral characteristics Range characteristicsAppendices Comet series 11 general characteristics Comet series 31 general characteristics Comet series 33 general characteristics Selection of cable cross-sections Schematic diagram for protection devices Selection of protection devices11.7 Connection of the cable shielding Glossary 12.2 6761200XT MGE UPS Systems S.A

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.