MGE UPS Systems Comet TM 5 - 30 kVA Overloads on 5 kVA Comet S11 or S31, When an overload occurs

Page 28

operation (cont')

"Static bypass"

3

overload curve

 

 

 

time

 

 

 

 

 

 

 

10 mn

 

 

 

 

 

 

 

1 mn

 

 

 

 

 

 

 

10 s

 

 

 

 

 

 

 

1 s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated load

0,15 s

 

 

 

 

 

 

current In

 

 

 

 

 

 

 

1,05

1,1

 

1,3

1,5

1,7

1,9

2

Fig. 22

overloads on 5 kVA Comet S11 or S31

For a major temporary overload (greater than 1.5In):

The load is transferred to AC input power via the "static bypass" 3 for 5 seconds. After that time, it is transferred back to the inverter.

If the overload persists, this sequence will be repeated 3 times in all before the inverter is shut down and the supply of power to the load interrupted.

For a minor overload:

Minor overloads can be supplied by the inverter for a duration defined in figure 21 for an ambient temperature of less than 30°C. Above this temperature, a derating coefficient k must be applied to the rated current and therefore to the overload curve in figure 21:

from 30°C to 35°C: k = 0.9,

from 35°C to 40°C: k = 0.85,

above 40°C: k = 0.8.

Example: an overload current I can be supplied by the inverter for 1 minute under the following conditions:

1.1 In < I < 1.3 In for an ambient temperature of 25°C,

1.1 x 0.9In < I < 1.3 x 0.9In for an ambient temperature of 32°C,

1.1 x 0.85In < I < 1.3 x 0.85In for an ambient temperature of 37°C,

1.1 x 0.8In < I < 1.3 x 0.8In for an ambient temperature of 42°C.

When an overload occurs:

the buzzer 17 sounds,

the orange "fault" light 19 goes on,

the inverter 7 shuts down at the end of its corresponding overload time,

the load is supplied by AC input power via the "static bypass" 3 ,

the green "load protected" light 21 goes off,

the red "load not protected" light 18 goes on.

The load is supplied via the "static bypass" 3 for 5 seconds, after which it is transferred back to the inverter. If the overload persists, the inverter shuts down and the supply of power to the load is interrupted.

6.4

Comet installation and user manual: E-6761200XT/FA

Merlin Gerin by MGE UPS SYSTEMS

Image 28
Contents Merlin Gerin Comet 30 kVASafety recommendations Norsk SikkerhedsforskrifterPortuguês Recomendações de segurançaSuomalainen TurvallisuusohjeetSvensk SäkerhetsföreskrifterContents Maintenance and servicing OptionsAppendices GlossarySafety information Identification to Comet ConfigurationIntroduction to Comet Identification plateFunctional diagram Key for figures 2 toFinal positioning figure GeneralComet layout seen from above Installation Special precautionsElectrical diagram for power connections Connection diagram for a single AC inputConnection of power cables figures 10 to Connection sequence for 5 kVA CometConnections for Comet series 11 5kVA Connections for Comet series 31 5kVAConnection sequence for Comet other than 5kVA Connections for Comet series 11 7.5/10kVAConnections for Comet series 31 7.5/10/15/20kVA Connections for Comet series 33 10/15/20/30kVAControls and indications Basic controls and indicationsControls and indications Key to figureThis light indicates that Comet is Buzzer Inverter on button Inverter off buttonControls and diagnostics display figure Buzzer resetFault reset Diagnostics displayPowering up to Comet Manual maintenance bypass switchStart-up Preliminary checksInverter start-upsystem in manual start-up mode Shutdown Powering downInverter shutdown Merlin Gerin by MGE UPS Systems Operation Operation on battery power figureNormal operation Battery duration Return of AC input powerBattery monitoring tests Inverter Overload curveOverloads on 5 kVA Comet S11 or S31 When an overload occursStatic bypass Overload curve Mains 2 out of tolerance Merlin Gerin by MGE UPS Systems Alarm indications table AlarmsStatus or action producing the indication Battery circuit breaker in off position End of battery powerChopper overtemperature see fault Manual bypassManual bypass switch SUB-D 15-pin connector connection SUB-D 15-pin connectorCommunication Standard functionsMonitor Plus ContactTalk Jbus / RS232 and Jbus / RS485Maintenance and servicing Safety reminder Preventive maintenance by userBattery maintenance Visual checkCustomer training Maintenance contractsAnnual check Additional battery cell characterisitics Extended battery cabinetOptions Connection of an additional battery cabinet Connection of an additional battery cabinetEmergency off Connection diagram for MX shunt trip to terminal block XR3Shunt trip connection Power connection diagrams Full galvanic isolation transformer standard Comet equipmentPower connection diagram Separate Mains 2 transformer AC bypass inputFrequency converter Hot standby system Harmonics filter Combined options Full isolation transformer and separate Mains 2 transformerFull isolation transformer and harmonics filter Example of a Comet seriesSeparate Mains 2 transformer and harmonics filter Relative positions of the various cubiclesRange characteristics General characteristicsAppendices Comet series 11 general characteristics Comet series 31 general characteristics Comet series 33 general characteristics Selection of cable cross-sections Schematic diagram for protection devices Selection of protection devices11.7 Connection of the cable shielding Glossary 12.2 6761200XT MGE UPS Systems S.A

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.