MGE UPS Systems Comet TM 5 - 30 kVA user manual Start-up, Preliminary checks, Powering up to Comet

Page 21

start-up

preliminary checks

check the settings of the protection devices:

input power switch 1 in off (O) position,

battery circuit breaker 4 in off (O) position,

"manual bypass" 8 switch set to "NORMAL" position (see figure 18);

check that nothing can block the ventilation system (air entry through the bottom and, where applicable, through the side vents);

check that there is a minimum 100mm clearance at the back for ventilation;

check that Comet no longer rests on its 4 wheels (lifting jacks in place);

check that the load-circuit circuit breakers (where applicable) are in off (O) position.

"manual maintenance bypass" switch

BY-PASS

NORMAL

TEST 2

Fig. 18

TEST 1

powering up to Comet

Caution:

As soon as AC input power is supplied to Comet (upstream circuit breaker on the low voltage switchboard in "on" position), the load is supplied via the "static bypass" 3 . No indications are given on the control panel.

bip...bip...

!

!

+ –

I O

17

21

22

put first the input power switch 1 and then the battery circuit breaker 4 in "on" position:

the buzzer 17 sounds,

the green "load protected" light 21 goes on,

the rectifier 2

and the charger 6 start up,

the inverter

7 automatically starts up, except if the system is in "manual

start-up" mode (optional). In this case, press the green "inverter on" button 22 .

Merlin Gerin by MGE UPS SYSTEMS

Comet installation and user manual: E-6761200XT/FA

4.1

Image 21
Contents Comet 30 kVA Merlin GerinSafety recommendations Sikkerhedsforskrifter NorskRecomendações de segurança PortuguêsTurvallisuusohjeet SuomalainenSäkerhetsföreskrifter SvenskContents Options Maintenance and servicingAppendices GlossaryConfiguration Safety information Identification to CometIntroduction to Comet Identification plateKey for figures 2 to Functional diagramGeneral Final positioning figureComet layout seen from above Special precautions InstallationElectrical diagram for power connections Connection diagram for a single AC inputConnection sequence for 5 kVA Comet Connection of power cables figures 10 toConnections for Comet series 31 5kVA Connections for Comet series 11 5kVAConnections for Comet series 11 7.5/10kVA Connection sequence for Comet other than 5kVAConnections for Comet series 33 10/15/20/30kVA Connections for Comet series 31 7.5/10/15/20kVABasic controls and indications Controls and indicationsControls and indications Key to figureThis light indicates that Comet is Inverter on button Inverter off button BuzzerBuzzer reset Controls and diagnostics display figureFault reset Diagnostics displayManual maintenance bypass switch Powering up to CometStart-up Preliminary checksInverter start-upsystem in manual start-up mode Powering down ShutdownInverter shutdown Merlin Gerin by MGE UPS Systems Operation on battery power figure OperationNormal operation Return of AC input power Battery durationInverter Overload curve Battery monitoring testsWhen an overload occurs Overloads on 5 kVA Comet S11 or S31Static bypass Overload curve Mains 2 out of tolerance Merlin Gerin by MGE UPS Systems Alarms Alarm indications tableStatus or action producing the indication End of battery power Battery circuit breaker in off positionManual bypass Chopper overtemperature see faultManual bypass switch SUB-D 15-pin connector SUB-D 15-pin connector connectionCommunication Standard functionsContact Monitor PlusTalk Jbus / RS232 and Jbus / RS485Safety reminder Preventive maintenance by user Maintenance and servicingBattery maintenance Visual checkMaintenance contracts Customer trainingAnnual check Extended battery cabinet Additional battery cell characterisiticsOptions Connection of an additional battery cabinet Connection of an additional battery cabinetConnection diagram for MX shunt trip to terminal block XR3 Emergency offShunt trip connection Full galvanic isolation transformer standard Comet equipment Power connection diagramsSeparate Mains 2 transformer AC bypass input Power connection diagramFrequency converter Hot standby system Harmonics filter Full isolation transformer and separate Mains 2 transformer Combined optionsFull isolation transformer and harmonics filter Example of a Comet seriesRelative positions of the various cubicles Separate Mains 2 transformer and harmonics filterGeneral characteristics Range characteristicsAppendices Comet series 11 general characteristics Comet series 31 general characteristics Comet series 33 general characteristics Selection of cable cross-sections Selection of protection devices Schematic diagram for protection devices11.7 Connection of the cable shielding Glossary 12.2 6761200XT MGE UPS Systems S.A

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.