MGE UPS Systems Comet TM 5 - 30 kVA user manual Emergency off, Shunt trip connection

Page 41

emergency off

shunt trip connection

Installation of an emergency off function must be carried out in compliance with applicable regulations. When an external emergency off function is activated, the AC input to Comet must be cut to ensure protection of life and property. However, this action does not cut the supply of power to the load protected by Comet because the system continues to operate on battery power.

To power down the entire installation via an emergency off function, the action must also turn off the following via a single device:

the battery circuit breaker 4 ;

the circuit breaker for the additional battery cabinet(s), if applicable;

and a circuit breaker placed downstream of the UPS, otherwise the UPS output remains live for approximately 3 seconds after the emergency off function has been activated.

This requires installation of an MX shunt trip.

check that the upstream circuit breaker on the low voltage switchboard is in "off" position;

check that the input power switch 1 and the battery circuit breaker 4 are in "off" position;

remove the connection cover panel 13 from the Comet;

supply the shunt trip coil with AC power across terminals 1 and 4;

terminals 2 and 3 may be used to supply (using a voltage identical to that of the

shunt trip) lights indicating the position of the battery circuit breaker 4 (breaking capacity of contacts is 1300VA);

once the connections are made, reposition the connection cover panel.

Connection diagram for MX shunt trip to terminal block XR3

 

 

Comet

 

1

4

2

3

emergency

 

 

 

off button

 

 

 

N

Ph

N

N

 

 

circuit

circuit

 

220 to 240V

breaker

breaker

 

50/60Hz

on light

off light

Comet XR3

battery emergency

terminal block

 

 

off

(exept Comet S11

 

 

 

L– L+

 

/ S31 of 5kVA)

 

1 2 3 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4

XR1/XR3

 

terminal block

 

for Comet

 

S11 / S31

 

of 5kVA

XR3 XR3 XR1

battery emerg. off Mains 2 (optional) secure the shielding of the cable to the stud provided on the connection cover panel (see appendices).

Merlin Gerin by MGE UPS SYSTEMS

Comet installation and user manual: E-6761200XT/FA

10.3

Image 41
Contents Comet 30 kVA Merlin GerinSafety recommendations Sikkerhedsforskrifter NorskRecomendações de segurança PortuguêsTurvallisuusohjeet SuomalainenSäkerhetsföreskrifter SvenskContents Options Maintenance and servicingAppendices GlossaryConfiguration Safety information Identification to CometIntroduction to Comet Identification plateKey for figures 2 to Functional diagramComet layout seen from above GeneralFinal positioning figure Special precautions InstallationElectrical diagram for power connections Connection diagram for a single AC inputConnection sequence for 5 kVA Comet Connection of power cables figures 10 toConnections for Comet series 31 5kVA Connections for Comet series 11 5kVAConnections for Comet series 11 7.5/10kVA Connection sequence for Comet other than 5kVAConnections for Comet series 33 10/15/20/30kVA Connections for Comet series 31 7.5/10/15/20kVABasic controls and indications Controls and indicationsControls and indications Key to figureThis light indicates that Comet is Inverter on button Inverter off button BuzzerBuzzer reset Controls and diagnostics display figureFault reset Diagnostics displayManual maintenance bypass switch Powering up to CometStart-up Preliminary checksInverter start-upsystem in manual start-up mode Inverter shutdown Powering downShutdown Merlin Gerin by MGE UPS Systems Normal operation Operation on battery power figureOperation Return of AC input power Battery durationInverter Overload curve Battery monitoring testsStatic bypass Overload curve When an overload occursOverloads on 5 kVA Comet S11 or S31 Mains 2 out of tolerance Merlin Gerin by MGE UPS Systems Status or action producing the indication AlarmsAlarm indications table End of battery power Battery circuit breaker in off positionManual bypass Chopper overtemperature see faultManual bypass switch SUB-D 15-pin connector SUB-D 15-pin connector connectionCommunication Standard functionsContact Monitor PlusTalk Jbus / RS232 and Jbus / RS485Safety reminder Preventive maintenance by user Maintenance and servicingBattery maintenance Visual checkAnnual check Maintenance contractsCustomer training Options Extended battery cabinetAdditional battery cell characterisitics Connection of an additional battery cabinet Connection of an additional battery cabinetShunt trip connection Connection diagram for MX shunt trip to terminal block XR3Emergency off Full galvanic isolation transformer standard Comet equipment Power connection diagramsSeparate Mains 2 transformer AC bypass input Power connection diagramFrequency converter Hot standby system Harmonics filter Full isolation transformer and separate Mains 2 transformer Combined optionsFull isolation transformer and harmonics filter Example of a Comet seriesRelative positions of the various cubicles Separate Mains 2 transformer and harmonics filterAppendices General characteristicsRange characteristics Comet series 11 general characteristics Comet series 31 general characteristics Comet series 33 general characteristics Selection of cable cross-sections Selection of protection devices Schematic diagram for protection devices11.7 Connection of the cable shielding Glossary 12.2 6761200XT MGE UPS Systems S.A

Comet TM 5 - 30 kVA specifications

MGE UPS Systems Comet TM 5 - 30 kVA is a reliable and efficient uninterruptible power supply (UPS) designed to ensure the smooth operation of critical systems in various applications. This UPS is particularly suited for data centers, telecommunications, and industrial environments that require high availability and robust power protection.

One of the main features of the Comet TM series is its modular design, which allows users to scale the UPS capacity as needed. This flexibility is crucial for businesses that anticipate growth or fluctuating power requirements. The UPS is available in a range of capacities, from 5 kVA to 30 kVA, allowing for tailored solutions that fit specific power needs.

The Comet TM is equipped with advanced double conversion technology, which provides clean and reliable power, isolating the connected equipment from input voltage disturbances. This technology ensures that any fluctuations in the mains supply, such as voltage sags or surges, do not affect the operation of sensitive electronic devices. Additionally, this UPS features a wide input voltage range that contributes to improved efficiency and reduced energy consumption.

An impressive aspect of the Comet TM is its high-efficiency mode, which optimizes energy consumption while maintaining power quality. This mode reduces operating costs and contributes to lower carbon footprints, making it an environmentally friendly choice. Furthermore, the UPS incorporates intelligent battery management systems, which enhance battery performance and extend their lifespan. This is essential in minimizing downtime and ensuring that backup power is readily available when needed.

The user-friendly interface of the Comet TM allows for easy monitoring and management of the system. With graphical displays and comprehensive alarms, users can promptly identify potential issues and take corrective actions. Remote management capabilities are also built into the system, enabling users to monitor and control the UPS remotely, which is particularly beneficial for businesses that operate across multiple locations.

In summary, the MGE UPS Systems Comet TM 5 - 30 kVA is designed for organizations that need reliable power protection and high efficiency. With its modular scalability, advanced double conversion technology, high-efficiency mode, intelligent battery management, and user-friendly interface, the Comet TM series stands out as a robust solution for critical power applications. Its combination of features ensures that businesses can maintain uninterrupted operations while benefiting from cost savings and a reduced environmental impact.