MGE UPS Systems GES-202L Computer Interface Port, Open Collector Dry Contact Communication

Page 15

Always “On” UPS Systems Inc.

Computer Interface Port

The computer interface port has the following characteristics:

The communication port on the back of the UPS may be connected to a host computer. This port allows the computer to monitor the status of the UPS and control the operation of the UPS. Its major functions include the following:

1.The ability to broadcast a warning when the power fails.

2.The ability to close any open files before the battery reserves are exhausted.

3.The ability to turn off the UPS.

4.The ability to make the UPS perform a self-test.

Some computers are equipped with a serial connector to link with the communication port, in some cases a special plug-in card may be needed.

Open Collector (Dry Contact) Communication

1.Pin 5 and 2 are open collector outputs that must be pulled up to a common referenced supply no greater than +40VDC.

2.The transistors are capable of a maximum non-conductive load of 25mADC, use pin 4 as the common.

3.Pin 5 generates a High to Low signal when the battery inside the UPS has less than 5 minutes back up time left.

4.Pin 2 generates a High to Low signal when the line has failed.

5.Pin 6 will shut down the UPS is a high is sustained for 0.36 seconds.

RS-232 Communication

6.Pin 6 is the RS-232 data input from computer (RX)

7.Pin 9 is the RS-232 data output to computer (TX).

8.Pin 7 is the common or computer ground

NOTE:

1.Switch rating +40V, 25mADC non-inductive.

2.Pin 7 should be connected to computer ground only.

15

Image 15
Contents Uninterruptible Power Supply Always On UPS Systems Inc Always On UPS Systems Inc Battery Replacement Troubleshooting Storage Introduction 36VDC Safety InstructionsFront Panel PresentationTELEPHONE/MODEM/ETHERNET Surge Protection Rear PanelSite Wiring Fault Indicators RED LED Installation Check the Site Wiring Fault Indicator Connecting the Telephone/Modem/Ethernet LinesOperation Audible Alarm Software Options UPSilon 2000 SoftwareInterface Kits Computer Interface Port Open Collector Dry Contact CommunicationRS-232 Communication Remove watches, rings, etc Use tools with insulated handles Battery ReplacementTroubleshooting Problems Possible causesSolution Storage Storage ConditionsExtended Storage Black RED Battery Bank InstallationSpecification SpecificationsGES-801LR GES-102LR GES-152LR GES-202LR GES-302LR Additional Purchases or Upgrades QA / Warranty QuestionsSoftware Questions