American Power Conversion MX28B1200, MX28B2400+27V Power Output Capacity, Rectifiers, Converters

Page 13

Rev 1

MX28B-1200+27V PRODUCT MANUAL

4.2 Power Output Capacity

A power frame consists of three rectifier shelves, each shelf accommodating up to four hot-plug, 100 amp rectifiers. A completely configured power frame with 12 rectifiers is rated at 1200 amps. The master control unit provides control and monitoring for the entire system.

The optional converter shelf supports up to eight hot-plug +24/-48V DC/DC converters. Each converter is rated at 10 Amps.

4.3 Rectifiers

APC Model MRF28H27BV with specifications as follows:

Input Voltage:

176-264V ac (230V ac nominal) @ 45-66 Hz

∙ Input Current per Rectifier:

13.9 Amps @ 230V ac

Apparent Power Factor:

99% Typical, 98% Minimum

Output Voltage:

27.2V DC

Overvoltage Protection:

Set at 31.5V DC

∙ Output Current per Rectifier:

100A Minimum Continuous

∙ Power Output per Rectifier:

2800W Continuous, Vin > 198V ac

Efficiency:

89% Typical

Cooling:

Fan cooled, front to rear airflow

Ambient Temperature:

-25°C to 55°C Operational

4.4 Converters

APC Vector Series with specifications as follows:

Input Voltage:

Input Current per converter:

Output Voltage:

Output current per converter:

Power output per converter:

Efficiency:

Cooling:

Ambient temperature:

+20V DC to +30V DC

<30 amps

-50VDC (-48V DC to –52V DC)

10amps

520Watts

>85%

Fan cooled, front to rear airflow -40°C to 55°C Operational

7

Image 13
Contents Model MX28B1200/2400+27V Description Part Number Battery Temperature ProbeDC Distribution Options +24V LVD Options +24VInitial release Revision Date Description 09/12/2001Table of Contents SETUP, ADJUSTMENTS, and Operation Page Introduction PrecautionsInspection upon Receipt of Goods GeneralReturn of Damaged Goods Concealed DamageWarranty Repair or Replacement Warranty ReturnsGeneral Provisions Exclusions and Limitations MX28B-1200/2400+27V DescriptionMX28B1200/2400+27V System Diagram Rectifiers Power Output CapacityConverters Control Unit AC Input Power+24V DC Distribution Battery connectionsDC Distribution 48 V DC Distribution from Converters OptionalMechanical EnvironmentalCompliance Preparation Safety PrecautionsRecommended Tools Recommended Test EquipmentMounting Room/LocationsVentilation AC Service and Ground ConnectionsBattery Disconnect Cable Sizing Considerations Connecting the CablesConverter Installation Rectifier InstallationAlarm Interface PC Board Alarm ConnectionsAlarm Outputs External Alarm InputsDC Circuit Breakers Connecting The Loads2.2 -48V Circuit Breaker Load Connections Installation of Circuit BreakersPower-Up and Checkout Battery Temperature Probe InstallationSystem Parameters Verification/Adjustment Apply AC PowerFull System Power Up User Interface SETUP, ADJUSTMENTS, and OperationAlarm Output Relays External Alarm InputsSnmp Interface Parameter Locations, Descriptions, and Default Values Status AlarmsSystem SET-ALM Date Setup PINOUT-RLY RLY-MAP AliasModules Rect SET-ALM DiagParam InfoFuse SET-ALM Cirbkr SET-ALMBatt SET-ALM Alias Fuse LVD SET-ALMComp PIN OEM Rev MX28B-1200+27V Product ManualParameter Description Display Screens Default Settings Conv LV Alm 40.0 C OFFBatt Disc Alm m+ Conv Fail Safem+ Cir Bkr 1 Alm m+ Out-Rly LVD2 LVD1