American Power Conversion MX28B1200, MX28B2400+27V manual Battery Connections, Battery Disconnect

Page 21

Rev 1

MX28B-1200+27V PRODUCT MANUAL

The AC input enclosure, located at the top rear of the MX28B housing, is provided with three pilot holes in the top for attaching external conduit (Figure 5-4), and three 1-inch conduits exiting the bottom for AC wire. AC wiring passing through the conduit will be routed through the access opening in the AC input enclosure into the wiring area where a safety ground bar and rectifier input terminal blocks are located. The terminal blocks are labeled as “L1” and “L2/N” for connection of the two AC wires (Figure 5-3). Each terminal block represents connections for all 4 rectifiers in the shelf.

The suggested wire size for L1, and L2 is #4 AWG rated at 105°C; however, the ambient temperature and number of wires in a conduit must also be considered in accordance with NEC requirements. Be sure to follow any local electrical wiring codes. Terminate the ground wire in the AC box at the top of the unit to the ground terminal block. Continue to run the remaining two wires into the individual conduits to each rectifier shelf. Connect them to L1, and L2 of the terminal block behind the access plate.

If the AC input power is provided from a three-phase distribution panel, the circuit breaker positions should be selected such that the load is balanced as much as possible.

Pilot holes (3)

Figure 5-4

5.3 Battery Connections

5.3.1Battery Disconnect

An external circuit breaker or fused disconnect (not supplied) is recommended in the positive line (located at the battery end) to protect the cables from the battery to the MX28B DC power plant. The power plant can monitor auxiliary contacts from this breaker. Selection of a circuit breaker or fuse for a battery string should take into account maximum battery short circuit current and cable sizing.

15

Image 21
Contents Model MX28B1200/2400+27V Description Part Number Battery Temperature ProbeDC Distribution Options +24V LVD Options +24VInitial release Revision Date Description 09/12/2001Table of Contents SETUP, ADJUSTMENTS, and Operation Page Introduction PrecautionsInspection upon Receipt of Goods GeneralReturn of Damaged Goods Concealed DamageWarranty Returns Warranty Repair or ReplacementGeneral Provisions Exclusions and Limitations MX28B-1200/2400+27V DescriptionMX28B1200/2400+27V System Diagram Power Output Capacity RectifiersConverters Control Unit AC Input Power+24V DC Distribution Battery connectionsDC Distribution 48 V DC Distribution from Converters OptionalEnvironmental MechanicalCompliance Preparation Safety Precautions Recommended Tools Recommended Test EquipmentMounting Room/LocationsVentilation AC Service and Ground ConnectionsBattery Disconnect Cable Sizing Considerations Connecting the CablesConverter Installation Rectifier InstallationAlarm Interface PC Board Alarm ConnectionsAlarm Outputs External Alarm InputsDC Circuit Breakers Connecting The Loads2.2 -48V Circuit Breaker Load Connections Installation of Circuit BreakersPower-Up and Checkout Battery Temperature Probe InstallationSystem Parameters Verification/Adjustment Apply AC PowerFull System Power Up User Interface SETUP, ADJUSTMENTS, and OperationExternal Alarm Inputs Alarm Output RelaysSnmp Interface Parameter Locations, Descriptions, and Default Values Alarms StatusSystem SET-ALM Date Setup PINOUT-RLY RLY-MAP AliasModules Rect SET-ALM DiagParam InfoFuse SET-ALM Cirbkr SET-ALMAlias Fuse LVD SET-ALM Batt SET-ALMComp PIN OEM Rev MX28B-1200+27V Product ManualParameter Description Display Screens Default Settings Conv LV Alm 40.0 C OFFBatt Disc Alm m+ Conv Fail Safem+ Cir Bkr 1 Alm m+ Out-Rly LVD2 LVD1