The AC input enclosure, located at the top rear of the MX28B housing, is provided with three pilot holes in the top for attaching external conduit (Figure
The suggested wire size for L1, and L2 is #4 AWG rated at 105°C; however, the ambient temperature and number of wires in a conduit must also be considered in accordance with NEC requirements. Be sure to follow any local electrical wiring codes. Terminate the ground wire in the AC box at the top of the unit to the ground terminal block. Continue to run the remaining two wires into the individual conduits to each rectifier shelf. Connect them to L1, and L2 of the terminal block behind the access plate.
If the AC input power is provided from a
Pilot holes (3)
Figure
5.3 Battery Connections
5.3.1Battery Disconnect
An external circuit breaker or fused disconnect (not supplied) is recommended in the positive line (located at the battery end) to protect the cables from the battery to the MX28B DC power plant. The power plant can monitor auxiliary contacts from this breaker. Selection of a circuit breaker or fuse for a battery string should take into account maximum battery short circuit current and cable sizing.