APC BR500CI-AS manual Troubleshooting, Specifications, Battery Replacement, Warranty, Service

Page 2

Troubleshooting

Problem

Probable Cause

Solution

 

 

 

Back-UPS will not turn on.

Circuit Breaker has tripped.

Reduce the amount of equipment plugged into the “Battery Backup + Surge Protection”

 

 

outlets. Reset the circuit breaker by pushing it back in.

 

Utility power is not available at the wall

Ensure the fuse or circuit breaker for the wall outlet is okay, and the wall switch controlling

 

outlet.

the wall outlet (if any) is in the ON position.

 

 

 

Connected equipment loses

The Back-UPS is overloaded.

Ensure the equipment plugged into the outlets of the unit are not overloading the capacity

power.

 

of the unit. Try disconnecting some of the equipment one device at a time, and see if the

 

 

problem continues.

 

The Back-UPS has exhausted its available

The unit can only operate on battery power for a limited amount of time. The unit will

 

battery power.

eventually turn off when the available battery power has been used. Allow the unit to

 

 

recharge for 10 hours before continuing to use the unit.

 

The equipment connected to the Back-UPS

The output waveform is designed for computers and computer-related equipment. It is not

 

does not accept the step-approximated sine

designed for use with motor-type equipment.

 

waveform from the unit.

 

 

The Back-UPS may require service.

Contact APC Technical Support for further troubleshooting.

The ON/OFF button is lit, and

The unit is using battery.

The unit is operating normally and using battery power. Save any current work, turn off all

the unit is beeping four times

 

equipment, and turn the unit OFF. Once normal power is restored, turn the unit back ON,

every 30 seconds, or it is

 

and turn on all equipment.

emitting a constant tone.

 

 

 

 

 

The On/Off button flashes once

Battery capacity is low (there is about 2

The unit is about to shut down due to a low battery charge condition! When the unit beeps

per second, and the Back-UPS

minutes of use remaining).

once every second, the battery has about 2 minutes of power remaining. Immediately

beeps once per second at the

 

power down your computer, and turn the unit OFF. When power returns to normal, the unit

same time.

 

will recharge the battery.

Inadequate runtime.

The battery is not fully charged.

Allow the unit to charge by leaving it plugged in, and switched on for 10 hours.

 

The battery is near the end of useful life.

As a battery ages, the amount of runtime available will decrease. Batteries also age

 

 

prematurely if the unit is placed near excessive heat. If the battery will not charge, the

 

 

Back-UPS is no longer operable.

 

 

 

Specifications

Input

Voltage

230 Vac nominal

 

 

 

 

Frequency

45-65 Hz

 

 

 

 

Brownout Transfer

160 ±8% VAC, typical

 

 

 

 

Over-voltage Transfer

280 VAC, typical

 

 

 

Output

UPS Capacity (total)

500 VA / 300 W

 

 

 

 

Voltage On Battery

230 Vac rms

 

 

(step-approximated sine wave)

 

 

 

 

Frequency - On Battery

50 Hz ±1 Hz, 60 Hz ±1 Hz

 

 

 

 

Transfer Time

50 Hz: 6ms typical, 10ms maximum

 

 

60 Hz: 5ms typical, 8ms maximum

 

 

 

Protection and

AC Surge Protection

Full time, 273 joules

Filter

 

 

AC Input

Re-settable circuit breaker

 

 

 

 

Battery

Type

Maintenance free

 

 

 

 

Average Life

2 - 5 years depending on the number of discharge cycles and

 

 

environmental temperature

 

 

 

 

Typical Recharge Time

10 Hours

 

 

 

Physical

Net Weight

5.4 kg

 

 

 

 

Dimensions (H x W x D)

18.55 cm (H) x 11.5 cm (W) x 21.3 cm (D)

 

 

 

 

Operating Temperature

0 oC to 40 oC (32 oF to 104 oF)

 

Storage Temperature

-15 oC to 45 oC (5 oF to 113 oF)

 

Operating Relative

0 to 95% non-condensing

 

Humidity

 

 

 

 

 

Operating Elevation

0 to 3000 m (0 to 10,000 ft)

 

 

 

Battery Replacement

The battery in the Back-UPS 500 is not user-replace- able. Contact APC Sales and Technical Support for a list of authorized service centers near you.

Warranty

The standard warranty is 2 years from the date of purchase. The APC standard procedure is to replace the original unit with a factory reconditioned unit. APC will ship the replacement unit once the defective unit is received by the repair department or cross-ship upon the provision of a valid credit card number. The customer pays for shipping to APC, and APC pays ground freight transportation costs back to the customer. Customers who must have the original unit back due to assigned asset tags and set depreciation schedules must declare such a need at first contact with APC Technical Support.

Service

Please DO NOT RETURN Back-UPS to the place of purchase under any circumstances.

1.Consult the Troubleshooting section to eliminate common problems.

2.If you still have problems or questions, please contact APC via the internet or at one of the phone numbers listed below.

3.Before contacting APC, please be sure to record the date purchased, UPS model, and serial number (on bottom of unit).

4.Be prepared to troubleshoot the problem over the telephone with a Technical Support Representative. If this is not successful, the representative will issue a Return Material Authorization Number (RMA#) and a shipping address.

5.Pack the unit in its original packaging. If the original packaging is not available, ask APC Technical Support about obtaining a new set. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty (insuring the package for full value is recommended).

6.Write the RMA# on the outside of the package.

7.Return the unit by insured carrier to the address given to you by APC Technical Support.

APC Worldwide Customer Support

Indonesia

0800 1088 088

Malaysia

1800 80 1030

Technical Support

http://www.apc.com/support

Philippines

1800 1651 0302

Internet

http://www.apc.com

Singapore

+65 6389 6823

Worldwide

+1 800 555 2725

Thailand

001 800 65 6340

 

 

Vietnam

(1201 0288) 1 888 576 6432

Image 2
Contents Status Indicators 2Connect the Battery and Turn on the UnitAdjusting Transfer Voltage and Sensitivity Settings Transfer Voltage and Sensitivity SettingsBattery Replacement TroubleshootingSpecifications Warranty3lập Độ nhạy Kết nối Thiết bị2Nối Ắc quy vào và Bật Bộ Lưu điện lên Điện áp Chuyển và Các Thiết lập Độ nhạyThay Ắc quy Xử lý trục trặcĐặc điểm kỹ thuật Bảo hành状态指示灯 连接设备2连接电池并启动装置 LED 闪烁状态可能的原因 解决方案 电池更换保修服务 2連接電池並開啟裝置 Power On LED連接設備 調整傳輸電壓和敏感度 狀態指示燈問題起因 解決方法