NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
High Bypass Point | +10% of | +5%, +10%, +15%, | Maximum voltage that the UPS | |
| output voltage | +20% | will pass to connected | |
| setting |
| equipment during internal | |
|
|
| bypass operation. | |
|
|
|
| |
Low Bypass Point | Minimum voltage that the UPS | |||
| voltage setting |
| will pass to connected | |
|
|
| equipment during internal | |
|
|
| bypass operation. | |
|
|
|
| |
Output Voltage | 230 VAC | 200, 208, 220, 230, | Allows the user to select the | |
|
| 240 VAC | output voltage while | |
|
|
|
| |
Output Frequency | Automatic | Automatic | Sets the allowable UPS output | |
| 50 ± 3 Hz or | 50 ± 3 Hz | frequency. Whenever possible, | |
| 50 ± 0.1 Hz | the output frequency tracks the | ||
| 60 ± 3 Hz | |||
| 60 ± 3 Hz | input frequency. | ||
|
| |||
|
| 60 ± 0.1 Hz |
| |
|
|
|
| |
Number of Batteries | 1 | Number of Connected | Defines the number of | |
|
| Batteries | connected batteries for proper | |
|
|
| run time prediction. | |
|
|
| Default setting of 1 = 1920 VAh | |
|
|
| (192 V x 10 Ah) | |
|
|
| Setting of 2 = 3840 VAh, etc. | |
|
|
|
|
12