American Power Conversion 240 VAC Function Factory User Selectable Description Default Choices

Page 14

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

 

output voltage

+20%

will pass to connected

 

setting

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

Low Bypass Point

-30% of output

-15%, -20%, -25%, -30%

Minimum voltage that the UPS

 

voltage setting

 

will pass to connected

 

 

 

equipment during internal

 

 

 

bypass operation.

 

 

 

 

Output Voltage

230 VAC

200, 208, 220, 230,

Allows the user to select the

 

 

240 VAC

output voltage while on-line.

 

 

 

 

Output Frequency

Automatic

Automatic

Sets the allowable UPS output

 

50 ± 3 Hz or

50 ± 3 Hz

frequency. Whenever possible,

 

50 ± 0.1 Hz

the output frequency tracks the

 

60 ± 3 Hz

 

60 ± 3 Hz

input frequency.

 

 

 

 

60 ± 0.1 Hz

 

 

 

 

 

Number of Batteries

1

Number of Connected

Defines the number of

 

 

Batteries

connected batteries for proper

 

 

 

run time prediction.

 

 

 

Default setting of 1 = 1920 VAh

 

 

 

(192 V x 10 Ah)

 

 

 

Setting of 2 = 3840 VAh, etc.

 

 

 

 

12

Image 14
Contents APC Smart-UPSRT UXI/UXICH Page Introduction 220/230/240 V Models Page Ethernet Port Battery Safety Connect the Ground and Wire the Battery System Connect Equipment and Power to the UPS Page Operation Bypass mode. Refer to Troubleshooting in this manual User Configurable Items Function Factory User Selectable Description Default Choices Connect the EPO Emergency Power OFF Battery Replacement Service Troubleshooting Bypass LED Illuminates Regulatory Agency Approvals and Radio Frequency Warnings Declaration of Conformity APC Worldwide Customer Support