THIRD PARTY BATTERY SOLUTION
Batteries must be Sealed
≥20,000 A.
Ensure that the external batteries are wired prior to connecting the batteries to the UPS.
Two separate, isolated 192 V battery systems are required when using a third party battery solution. One cable assembly must be wired to each 192 V battery system. Two cable assemblies are included with the UPS, one for each 192 V battery system.
Connect the Ground and Wire the Battery System
1.Connect the ground wires (included), to each battery enclosure ground and the TVSS screw on the back of the UPS.
2.Cut off one of the connectors on each cable assembly revealing the positive and negative wires in each cable.
3.Connect the positive (red), and negative (black) wires to the positive and negative terminals on each external battery system. Ensure that the proper polarities are connected.
4.Plug the cable connectors into the battery connector receptacles on the back of the UPS.
Battery
System 1
Battery
System 2
6