American Power Conversion 8000 VA, 220 VAC, 240 VAC Connect the Ground and Wire the Battery System

Page 8

THIRD PARTY BATTERY SOLUTION

Batteries must be Sealed Lead-Acid type. Use 50 A, 250 VDC fuses with an Interrupt rating of

20,000 A.

Ensure that the external batteries are wired prior to connecting the batteries to the UPS.

Two separate, isolated 192 V battery systems are required when using a third party battery solution. One cable assembly must be wired to each 192 V battery system. Two cable assemblies are included with the UPS, one for each 192 V battery system.

Connect the Ground and Wire the Battery System

1.Connect the ground wires (included), to each battery enclosure ground and the TVSS screw on the back of the UPS.

2.Cut off one of the connectors on each cable assembly revealing the positive and negative wires in each cable.

3.Connect the positive (red), and negative (black) wires to the positive and negative terminals on each external battery system. Ensure that the proper polarities are connected.

4.Plug the cable connectors into the battery connector receptacles on the back of the UPS.

Battery

System 1

Battery

System 2

6

Image 8
Contents APC Smart-UPSRT UXI/UXICH Page Introduction 220/230/240 V Models Page Ethernet Port Battery Safety Connect the Ground and Wire the Battery System Connect Equipment and Power to the UPS Page Operation Bypass mode. Refer to Troubleshooting in this manual User Configurable Items Function Factory User Selectable Description Default Choices Connect the EPO Emergency Power OFF Battery Replacement Service Troubleshooting Bypass LED Illuminates Regulatory Agency Approvals and Radio Frequency Warnings Declaration of Conformity APC Worldwide Customer Support