American Power Conversion 240 VAC, 8000 VA, 220 VAC, 10000 VA user manual

Page 10

TERMINAL MODE TO CONFIGURE UPS PARAMETERS AND PROGRAM THE NUMBER OF BATTERY PACKS

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable from the computer to the serial com connector on the back of the UPS. Instructions for use with PowerChuteNetwork Shutdown software:

1.Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.

2.Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

9bits per second - 2400

9data - bits 8

9parity - none

9stop bit - 1

9flow control - none

Press ENTER

3.Example for setting the number of external battery packs:

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears on the screen prior to typing the next character.

Network Management card defaults:

User Name: apc

Password: apc

Press 1 and ENTER to select Device Manager.

Select the model by entering the corresponding number, then press Enter.

Press 3 and ENTER to select Configuration.

Press 1 and ENTER to select Battery.

Press 2 and ENTER to change the Battery Settings.

Type in the number of external battery packs.

Number of packs: 1= 1920 VAh, 2 = 3840 VAh, 3 = 5760 VAh, etc.

Press 3 and ENTER to accept the changes.

Press ESC multiple times (5) to return to the main menu.

Press 4 and ENTER to log out.

8

Image 10
Contents APC Smart-UPSRT UXI/UXICH Page Introduction 220/230/240 V Models Page Ethernet Port Battery Safety Connect the Ground and Wire the Battery System Connect Equipment and Power to the UPS Page Operation Bypass mode. Refer to Troubleshooting in this manual User Configurable Items Function Factory User Selectable Description Default Choices Connect the EPO Emergency Power OFF Battery Replacement Service Troubleshooting Bypass LED Illuminates Regulatory Agency Approvals and Radio Frequency Warnings Declaration of Conformity APC Worldwide Customer Support